SARASOTA, FL ·
OSHA Inspection: WEST FLORIDA DISTRIBUTORS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of WEST FLORIDA DISTRIBUTORS in 4500 CARMICHAEL AVE, SARASOTA, FL 34234 (NAICS 327991). OSHA activity number 339278707.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WEST FLORIDA DISTRIBUTORS
- Site address
- 4500 CARMICHAEL AVE
- City
- SARASOTA
- State
- FL
- ZIP
- 34234
- Mailing
- 4500 CARMICHAEL AVE, SARASOTA, FL 34234
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327991
- Employees
- 30
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.106 E06 II
- Issued
- Nov 19, 2013
- Penalty
- Initial $2,100 · Current $1,260 Reduced
General-duty citation text
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), was dispensed into containers without the nozzle and container being electrically interconnected. a) At the Outside Finishing Area - A 55 gallon drum of Acetone is stored in a flammable storage cabinet. The drum was not grounded, on or about, 08/09/13.
Recent events (2)
- · I (S) $1260
- · Z (S) $2100
1910.147 C04 I
- Issued
- Nov 19, 2013
- Abate by
- Feb 21, 2014
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) at the Granite Shop, the lockout program did not list specific procedural steps for the control of potentially hazardous energy prior to performing maintenance on machinery and equipment such as, but not limited to, bridge saws, CNC machine, edger, flat polisher, and wire saw, on or about, 11/06/13.
Recent events (3)
- · Z $2500
- · I (S) $2100
- · Z (S) $3500
1910.303 C03 I
- Issued
- Nov 19, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of the conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose. a) at the Hand Fabrication Area for a Makita Hand Sander (Serial # 205647A), in that, hand sander's power cord was spliced into an electrical extension cord and covered with tape, on or about, 11/07/13.
Recent events (2)
- · I (S) $1680
- · Z (S) $2800
1910.305 B02 I
- Issued
- Nov 19, 2013
- Abate by
- Dec 4, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) at the Outside Finishing Area - Hand Fabrication Area, electrical duplex outlets designed for a wet location were missing covers, on or about, 11/07/13.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G02 I
- Issued
- Nov 19, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) at the Granite Shop - Main Electrical Service Area, in that, bussbars were exposed within breaker box, on or about, 08/09/13.
Recent events (2)
- · I (S) $1680
- · Z (S) $2800
1910.304 G05
- Issued
- Nov 19, 2013
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) at the Hand Fabrication Area for a six foot pedestal fan, in that, the fan was powered by an electrical extension cord which was missing a ground pin, on or about, 11/07/13.
Recent events (2)
- · I (S) $1680
- · Z (S) $2800
More inspections at West Florida Distributors
View West Florida Distributors's full OSHA safety record →
More inspections in this industry (NAICS 327991)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339278707.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.