OSHKOSH, WI —
OSHA Inspection: ADM GRAIN COMPANY - OSHKOSH ELEVATOR
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ADM GRAIN COMPANY - OSHKOSH ELEVATOR in 3000 CLAIRVILLE RD., OSHKOSH, WI 54904 (NAICS 493130). OSHA activity number 339289241.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADM GRAIN COMPANY - OSHKOSH ELEVATOR
- Site address
- 3000 CLAIRVILLE RD.
- City
- OSHKOSH
- State
- WI
- ZIP
- 54904
- Mailing
- 3000 CLAIRVILLE RD., OSHKOSH, WI 54904
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493130
- Employees
- 9
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.272 J01
- Issued
- Jan 7, 2014
- Abate by
- Feb 13, 2014
- Penalty
- Initial $5,610 · Current $0 Reduced
E101E200M104
General-duty citation text
29 CFR 1910.272(j)(1): The employer did not develop and implement a written housekeeping program that established the frequency and the method(s) determined best to reduce accumulations of fugitive grain dust on ledges, floors, equipment, and other exposed surfaces: On 8/14/2013 in the canvas-topped building (known on site as the circus tent), there was a visible layering and buildup of grain dust on piles of wheat and corn, and on stored materials in the west end of the building. At least 1 inch of grain dust was observed as an accumulation on the east side of the corn pile. a.) The company's Housekeeping Program did not include timely inspections (e.g., after loading/unloading activities) or special controls that would have identified excessive accumulation of grain dust on pile surfaces. b.) The company's Housekeeping Program did not identify any method to prevent or clean-up grain dust on grain piles and other surfaces in this building, except for a reference to dry sweeping floor areas. This area was periodically used for open grain transfer including truck dumping and grain conveyor loading which creates dust clouds. The dust accumulations from the suspended dust can occur on multiple surfaces. Abatement Certification and Documentation is required.
Recent events (2)
- — I (S) $0
- — Z (S) $5610
1910.305 B02 I
- Issued
- Jan 7, 2014
- Abate by
- Feb 13, 2014
- Penalty
- Initial $3,740 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) On 8/14/2013 in the canvas-topped building (known on site as the circus tent) used for grain storage, the structure was equipped with a garage door and an electrical door opener that was connected to an interior plug-in outlet which was not equipped with a cover plate. There was visible dust within the outlet enclosure. The unprotected outlet would create the potential for contact with live parts whenever the plug was handled. Abatement Certification and Documentation is required.
Recent events (2)
- — I (S) $0
- — Z (S) $3740
1910.305 G01 IV A
- Issued
- Jan 7, 2014
- Abate by
- Feb 13, 2014
- Penalty
- Initial $0 · Current $0
E101E200M104
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) In the canvas-topped building (known on site as the circus tent) used for grain storage, the structure was equipped with a garage door and an electrical door opener which was connected via a flexible cord to an interior plug-in outlet. On and before 8/14/2013, the flexible cord as temporary wiring was not approved for use in lieu of permanent wiring. Abatement Certification and Documentation is required.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.307 C02 I
- Issued
- Jan 7, 2014
- Abate by
- Feb 28, 2014
- Penalty
- Initial $0 · Current $2,244
E101E200M104
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: a) On and before 8/14/2013, in the canvas-topped building (known on site as the circus tent) used for grain storage, electrical wiring and equipment, including a garage door opener, were not approved for Class II, Division 1 or Division 2 locations. The facility included a layer of settled dust in quantities sufficient to produce explosive or ignitable mixtures on part of the corn grain pile and other surface areas. The building was used for open grain transfer including truck dumping and grain conveyor loading which generates dust clouds during that process. Abatement Certification and Documentation is required.