Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BUREAU OF INDIAN AFFAIRS - CARSON

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF INDIAN AFFAIRS - CARSON in 311 E. WASHINGTON STREET, CARSON CITY, NV 89701 (NAICS 923130). OSHA activity number 339301301.

Watch Bureau OF Indian Affairs - Carson — free Get an email when a new federal OSHA severe-injury report for Bureau OF Indian Affairs - Carson is published. One employer, no account, unsubscribe in one click.
Site address
311 E. WASHINGTON STREET
City
CARSON CITY
State
NV
ZIP
89701
Mailing
311 E. WASHINGTON STREET, CARSON CITY, NV 89701
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923130
Employees
35
Ownership type
D

6 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) On or about August 7, 2013, in the admin officer's, fuduciary officer and law enforcement receptionist's office spaces, exit/egress 21-22 inches and was obstructed by a desk, file cabinet  and furniture.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit."  (a) On or about August 7, 2013, the door in room 128A office space, was not labeled or marked "EXIT."
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  (a) On or about August 7, 2013, two portable fire extinguishers were left free standing in the law enforcement receptionist's desk and not secured.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 7 instances 11 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  (a) On or about August 7, 2013, two re-locatable power taps were daisy chained, one connected to the other and used to plug-in a Cuisinart coffee maker, inverter panasonic water heater, microwave oven and refrigerator.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  (a) On or about August 7, 2013, the wall rectangular box with energized conductors did not have a cover in the I.T. spaces.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 3 instances 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  (a) On or about August 7, 2013, extension cords were used to extend power to the fan and surge protectors for more than 90 days.
Recent events (1)
  • — Z (S) $0

DF