MINDEN, NV ·
OSHA Inspection: VETERANS ADMINISTRATION, CARSON VALLEY OUTPATIENT CLINIC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VETERANS ADMINISTRATION, CARSON VALLEY OUTPATIENT CLINIC in 925 IRONWOOD DRIVE, STE 2102, MINDEN, NV 89423 (NAICS 923140). OSHA activity number 339301475.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 925 IRONWOOD DRIVE, STE 2102
- City
- MINDEN
- State
- NV
- ZIP
- 89423
- Mailing
- 925 IRONWOOD DRIVE, STE 2102, MINDEN, NV 89423
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 923140
- Employees
- 45
- Ownership type
- Federal government (D)
Citations
3 citations on file for this inspection.
1910.36 G02
- Issued
- Sep 30, 2013
- Abate by
- Oct 24, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) On or about August 7, 2013, in rooms 12 and 27, exit/egress were 20 and 21 inches wide and obstructed by desk, table and metal file cabinet.
Recent events (1)
- · Z (S) $0
1910.304 F01 IV
- Issued
- Sep 30, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel. (a) On or about August 7, 2013, in room 28, access to the power panel 2B was obstructed by a walker/wheel chair.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- Sep 30, 2013
- Abate by
- Oct 24, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose. (a) On or about August 7, 2013, in the nurses office room 9, the energized wall outlet receptacle's cover was broken.
Recent events (1)
- · Z (S) $0
More inspections in this industry (NAICS 923140)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339301475.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.