BUZZARDS BAY, MA ·
OSHA Inspection: P & S CONSTRUCTION, INC.
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of P & S CONSTRUCTION, INC. in OTIS AIR NATIONAL GUARD BASE BUILDING 131, BUZZARDS BAY, MA 02542 (NAICS 236220). OSHA activity number 339302887.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- P & S CONSTRUCTION, INC.
- Site address
- OTIS AIR NATIONAL GUARD BASE BUILDING 131
- City
- BUZZARDS BAY
- State
- MA
- ZIP
- 02542
- Mailing
- 11 SCHOOL STREET, N CHELMSFORD, MA 01863
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 200
- Ownership type
- Private (A)
Citations
1 citation on file for this inspection.
1926.150 F01
- Issued
- Oct 18, 2013
- Abate by
- Dec 10, 2013
- Penalty
- Initial $4,500 · Current $2,000 Reduced
General-duty citation text
29 CFR 1926.150(f)(1): Fire walls and exit stairways, required for the completed buildings, were not given construction priority. Fire doors, with automatic closing devices, were not hung on openings as soon as practicable. (a) Location - Building 131; ATCT Exit Stairway: On or about 07/19/13, the single exit stairway of an occupied air traffic control tower was not maintained, due to the fact that a fire rated door from the ETVS Room leading into the exit on the 7th floor had been removed, and not replaced to prevent the spread of fire and smoke. (b) Location - Building 131; ATCT Exit Stairway: On or about 07/19/13, the single exit stairway of an occupied air traffic control tower was not maintained, due to the fact that newly installed fire doors on levels 1, 2, 4 - 6 did not latch, nor have self closing devices to prevent the spread of fire and smoke.
Recent events (2)
- · I (O) $2000
- · Z (S) $4500
More inspections at P & S Construction, INC.