Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: NEVADA AIR NATIONAL GUARD - RENO

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NEVADA AIR NATIONAL GUARD - RENO in 1776 NATIONAL GUARD WAY, RENO, NV 89502 (NAICS 488190). OSHA activity number 339305856.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Nevada AIR National Guard - Reno for free Get an email when a new federal OSHA severe-injury report for Nevada AIR National Guard - Reno is published. One employer, no account, unsubscribe in one click.
Site address
1776 NATIONAL GUARD WAY
City
RENO
State
NV
ZIP
89502
Mailing
1776 NATIONAL GUARD WAY, RENO, NV 89502
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
500
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) On or about August 8, 2013, in the upper level of Bldg. 9, room 217 office space, exit/egress was 21 inches and obstructed by desk furniture and file cabinet.
Recent events (1)
  • · Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 8 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  (a) On or about August 8, 2013, in Bldg 118, room 118, a portable fire extinguisher was free standing by the door.
Recent events (1)
  • · Z (S) $0

1910.253 B04 III

Serious Gravity 5 2 instances 8 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  (a)  On or about August 8, 2013, in the maintenance room 109, oxygen, acetylene and nitrogen gas cylinders were stored within 3 feet of each other.
Recent events (1)
  • · Z (S) $0

1910.303 B01

Serious Gravity 1 1 instance 8 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees.  (a) On or about August 8, 2013, in Bldg. 9, Rm 132, the 220 volts wall receptacle with energized conductors was loose.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 8 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  (a) On or about August 8, 2013, in the upper level of Bldg 9, Rm 226, high amperage equipment such as Magic Chef Microwave Oven were plugged into the re-locatable power tap.
Recent events (1)
  • · Z (S) $0

1910.304 B03 I

Serious Gravity 5 1 instance 20 exposed
Issued
Oct 21, 2013
Abate by
Nov 14, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel.  (a)  On or about August 8, 2013, in the upper level of Bldg. 9, Class/Break Rm 257, sink outlets receptacles did not have ground fault circuit interruption (GFCI) protection.
Recent events (1)
  • · Z (S) $0

1910.304 F01 IV

Serious Gravity 5 2 instances 8 exposed
Issued
Oct 21, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.  (a) On or about August 8, 2013, in the Repair and Reclamation shop of Bldg. 9, power panels RRS-L and RRSL were obstructed by tool boxes and FOD cans.