Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: SEDALIA MACHINE WORKS INC.*

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SEDALIA MACHINE WORKS INC.* in 415 MARSHALL STREET, SEDALIA, MO 65302 (NAICS 332322). OSHA activity number 339329492.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sedalia Machine Works INC.* for free Get an email when a new federal OSHA severe-injury report for Sedalia Machine Works INC.* is published. One employer, no account, unsubscribe in one click.
Site address
415 MARSHALL STREET
City
SEDALIA
State
MO
ZIP
65302
Mailing
P.O. BOX 1363, SEDALIA, MO 65302
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332322
Employees
28
Ownership type
Private (A)

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 30, 2013
Abate by
Oct 25, 2013
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   (a) In the southwest corner of the plant a metal fourplex box was used as the end of an extension cord.  The box contained knockouts and was improperly used as part of an extension cord.  This use could result in an electrical shock hazard to employees.   Abatement verification not required, the employer has provided evidence of abatement.
Recent events (2)
  • · I (S) $1960
  • · Z (S) $2800

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Sep 30, 2013
Abate by
Oct 25, 2013
Penalty
Initial $2,800 · Current $1,960 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    (a) On the west wall of the plant a 240 volt electrical box feeding a dry transformer, had unguarded holes from missing breakers and 2" diameter knockouts posing an electrical shock hazard to employees.  The door to the box was open and accessible to employees.   Abatement verification is not required for this item.  The employer has provided evidence of abatement.
Recent events (2)
  • · I (S) $1960
  • · Z (S) $2800

1910.305 G02 III

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 30, 2013
Abate by
Oct 25, 2013
Penalty
Initial $2,100 · Current $1,470 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a)  In the south center area of the shop, the power cord to a portable plasma cutter was not protected from abrasion of its power conductors due to the strain relief fitting coming loose.  Employees were exposed to electrical shock hazards.  Abatement verification is not required for this item.  The employer has provided proof of abatement.
Recent events (2)
  • · I (S) $1470
  • · Z (S) $2100

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339329492.