Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,192,068Inspections Most recent open 2026-08-04 Last loaded 2026-08-07

OSHA Inspection: PROGRESSIVE SOLUTIONS

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of PROGRESSIVE SOLUTIONS in 9904 FM 812, AUSTIN, TX 78719 (NAICS 561990). OSHA activity number 339343832.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Progressive Solutions for free Get an email when a new federal OSHA severe-injury report for Progressive Solutions is published. One employer, no account, unsubscribe in one click.
Site address
9904 FM 812
City
AUSTIN
State
TX
ZIP
78719
Mailing
9904 FM 812, AUSTIN, TX 78719
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561990
Employees
76
Ownership type
A

7 citations on file for this inspection.

1910.215 A04

Serious Gravity 5 1 instance 10 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  On or about August 20, 2013, the distance between the grinding wheel periphery and the adjustable work rest on the Porter Cable grinder used by Maintenance employees had a gap between the wheel and work rest that measured approximately five-eighths (5/8)  inch, exposing employees to the hazard of being caught in the rotating wheel.
Recent events (2)
  • · I (S) $2400
  • · Z (S) $4000

1910.215 B09

Serious Gravity 5 1 instance 10 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  On or about August 20, 2013, the distance between the grinding wheel periphery and the adjustable tongue guard on the Porter Cable grinder used by Maintenance employees had a gap between the wheel and tongue guard that measured approximately one inch, exposing employees to the hazard of being struck by flying debris in the event of wheel breakage.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 1 2 instances 40 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  On or about August 20, 2013, the junction box covers were missing on the following boxes, exposing employees to an electrical hazard:    a:  The box containing the SHURflo, model 4UN54, pump for the steam cleaner was missing the box cover, exposing bare conductors.    b:  At the junction box for the fuel shutoff control, the cover was missing in the maintenance area.
Recent events (2)
  • · I (S) $1800
  • · Z (S) $3000

1910.305 G01 IV A

Serious Gravity 1 1 instance 10 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  On or about August 20, 2013, an extension cord in the maintenance area was used permanently at 110 volts to power a surge protector, which was used to power computer equipment, exposing employees to an electrical shock hazard.
Recent events (2)
  • · I (S) $1800
  • · Z (S) $3000

1910.305 G01 IV B

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  On or about August 20, 2013, the flexible cord powering a surge protector which, in turn, powered a radio in the truck wash area was run through the wall and plugged into an outlet in another room, exposing employees to an electrical shock hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 II

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:  On or about August 20, 2013, the flexible cord powering the 110 volt SHURflo, model 4UN54, pump had a splice, exposing employees to an electrical hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 J02 IV

Serious Gravity 1 2 instances 11 exposed
Issued
Oct 24, 2013
Abate by
Nov 8, 2013
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  On or about August 20, 2013, electrical outlets were used in wet locations without a ground fault interruption circuit (GFCI) at either outlet or the breaker panel in the following instances, exposing employees to an electrical hazard:    a:  The receptacle box in the maintenance area powering the water fountain next to the sink was not a GFCI outlet.      b:  A surge protector was used in the truck wash area to power a radio.  The cord for the surge protector ran through the wall and into an outlet in another room.  Neither the outlet nor the surge protector had a GFCI.
Recent events (2)
  • · I (S) $1800
  • · Z (S) $3000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339343832.