FORNEY, TX ·
OSHA Inspection: FURNITURE N CABINETS
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FURNITURE N CABINETS in 11604 US HWY. 80, FORNEY, TX 75126 (NAICS 423210). OSHA activity number 339396541.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FURNITURE N CABINETS
- Site address
- 11604 US HWY. 80
- City
- FORNEY
- State
- TX
- ZIP
- 75126
- Mailing
- 11604 US HWY. 80, FORNEY, TX 75126
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423210
- Employees
- 13
- Ownership type
- A
Citations
12 citations on file for this inspection.
1910.22 A01
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms, and service rooms were not kept clean and orderly and in a sanitary condition: The employer did not ensure that equipment, walls and ledges are kept free from hazardous accumulations of a class II combustible saw dust, exposing employees to the hazards of fire, deflagration and explosion. This violation was observed on September 4, 2013, and at time after thereto, in the Door Shop; where saw dust had accumulated on equipment, walls, and ledges.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.22 A02
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(2): The floor of every workroom was not maintained in a clean and, so far as possible, a dry condition: The employer did not ensure that workroom floors are kept free of hazardous accumulations of a class II combustible dust, exposing employees to the hazards of fire, deflagration, and explosion. This violation was observed on September 4, 2013, and at times after thereto, in the Door Shop; where saw dust had accumulated on the workroom floors.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.178 C02 VI A
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.178(c)(2)(vi)(a): The employer did not provide powered industrial trucks designated as EX for use in an atmosphere in which combustible dust is or may be in suspension continuously, intermittently, or periodically under normal operating conditions, in quantities sufficient to produce explosive or ignitable mixtures, or where mechanical failure or abnormal operation of machinery or equipment might cause such mixtures to be produced: The employer did not ensure only approved power operated industrial truck designated as EX was used in atmospheres in which combustible dust was present. This violation occurred on September 4, 2013, and at times prior thereto, in the shops; where employee operated Toyota forklift that was not designated as EX, in area with a class II combustible.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.178 L01 I
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l): This violation was occurred on or about September 4, 2013, and at time prior thereto, when employee was operating powered industrial truck and had not been certified in their safe operation.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.242 A
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.242(a): Hand and portable powered tools or equipment were not kept in safe condition: The employer did not ensure portable powered tools had safety device installed. This violation occurred on September 4, 2013, and at times prior thereto, in the Door Shop; where at least one (1) employee used Senco nail gun without safety contact tip.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.303 B02
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: The employer did not ensure electrical equipment is used and installed in accordance with the listing or lableling instructions. This violation was observed on or about September 4, 2013: a) In the Door shop, a metal electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord powering a Grizzly 220V, MD 8854549. b) In the Door shop a metal electrical receptacle box designed to be installed inside of a wall was used on the end of an extension cord powering a BalDor stock feeder.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.304 G05
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $1,600 · Current $600 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: This violation occurred on September 4, 2013, in the Door Shop; where employees were exposed to electrical hazards while using table fan "King of Fan" that was missing ground pin.
Recent events (2)
- · I (S) $600
- · Z (S) $1600
1910.305 B01 II
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: The employer did not close unused openings on electrical equipment. This violation was observed on or about September 4, 2013, in the Door Shop, where: a) A metal electrical receptacle box at the Part table used to provide power to portable powered tools had opening at the knock-out; b) A metal electrical receptacle box was used on the end of an extension cord powering a Grizzly 220V, MD 8854549 had opening at the knock-out; c) A metal electrical receptacle box was used on the end of an extension cord powering a BalDor Stock Feeder had opening at the knock-out.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.305 G02 II
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,000 · Current $800 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: The employer did not ensure flexible cords were used only in continuous length without splice. This violation was observed on or about September 4, 2013, in the Cabinet Shop; where employees were exposed to electrical hazards from using flexible cords with splices. a) Electrical cord from a Dado table saw was spliced; b) Electrical cord from a Hampton Bay Fan was spliced.
Recent events (2)
- · I (S) $800
- · Z (S) $2000
1910.305 G02 III
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $1,600 · Current $600 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: The employer did not ensure flexible cords were connected to devices and fittings so that tension was not transmitted to joints or terminal screws. This violation was observed on or about September 4, 2013: a) In the Door Shop, where the flexible cord of a metal electrical receptacle box used to power a BalDor stock feeder did not have strain relief device causing a transmission of tension to joints and or terminals; b) In the Cabinet Shop, where the flexible cord used to power a Dado table saw did not have strain relief device causing a transmission of tension to joints and or terminals.
Recent events (2)
- · I (S) $600
- · Z (S) $1600
1910.307 C02 I
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $2,800 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: The employer did not ensure that equipment is approved for the class of location, and for the ignitable or combustible properties of the saw dust. This violation occurred on September 4, 2013, and at times prior thereto, in the Door Shop; where circuit breaker boxes, gang boxes, disconnect switches, and receptacles were not dust-tight ignition proof and approved for class II locations.
Recent events (2)
- · I (S) $1000
- · Z (S) $2800
1910.334 A02 II
- Issued
- Feb 28, 2014
- Abate by
- Mar 12, 2014
- Penalty
- Initial $1,600 · Current $600 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service: The employer did not remove from service damaged extension cords. This violation was most recently observed on or about September 4, 2013: a) In the Cabinet Shop, where an electrical extension cord used to power a 6-foot ABC fan had damaged insulation; b) In the Cabinet Shop, where an electrical extension cord used to power a Hampton Bay fan had damaged insulation; c) In the Cabinet Shop, where an electrical extension cord used to power a Utilitech fan had damaged insulation; d) In the Door shop, where an electrical extension cord used to power a dust collector Grizzly Industrial had damaged insulation; e) In the Door Shop, where an electrical extension cord used to power a Porter Cable Sander had damaged insulation.
Recent events (2)
- · I (S) $600
- · Z (S) $1600
More inspections in this industry (NAICS 423210)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339396541.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.