OSHA Inspection: ROGERS HELICOPTERS INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of ROGERS HELICOPTERS INC. in ENTERGY STRUCTURE 197, PERRYVILLE, AR 72126 (NAICS 221121). OSHA activity number 339415077.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rogers Helicopters INC. for free Get an email when a new federal OSHA severe-injury report for Rogers Helicopters INC. is published. One employer, no account, unsubscribe in one click.
Site address
ENTERGY STRUCTURE 197
City
PERRYVILLE
State
AR
ZIP
72126
Mailing
P.O. BOX 4, CLOVIS, CA 93613
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221121
Employees
45
Ownership type
A

8 citations on file for this inspection.

1910.269 A02 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $6,300 · Current $0 Reduced
29 CFR 1910.269(a)(2)(i): Employees were not trained in nor were they familiar with the safety-related work practices, safety procedures, and other safety requirements that pertained to their respective job assignments:     On or about September 15, 2013, at the jobsite at or near Entergy tower 197, north of Alpine, Arkansas, employees were replacing insulators on shield wires above 500,000 volt transmission lines. The employees had not been trained on safety requirements pertaining to the tasks they were performing, exposing the employees to electrocution hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $6300

1910.269 A03

Serious Gravity 10 2 instances 4 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.269(a)(3): The employer did not determine existing conditions related to the safety of the work to be performed before work on or near electric lines or equipment was started:     On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas,  employees were replacing insulators on shield wires above 500,000 volt transmission lines. The employees did not determine if induced voltage was present on the shield wires, prior to installing the grounds. This condition exposed the employees to the hazard of electrocution in the following instances:     a) The shield wire on the north side of the lattice tower   b) The shield wire on the south side of the lattice tower
Recent events (2)
  • · I (S) $4900
  • · Z (S) $7000

1910.269 C

Serious Gravity 10 1 instance 4 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $6,300 · Current $4,410 Reduced
29 CFR 1910.269(c): The employee in charge did not conduct a job briefing with the employees involved before they started each job, including at least the following subjects: hazards associated with the job, work procedures involved, special precautions,      On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas, employees were replacing insulators on shield wires above 500,000 volt transmission lines. The employee in charge did not brief the employees on the hazards associated with induced current, exposing employees to electrocution hazards.
Recent events (2)
  • · I (S) $4410
  • · Z (S) $6300

1910.269 C02 II

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.269(c)(2)(ii): An extensive briefing was not conducted in instances where the employee could not be expected to recognize and avoid the hazards involved in the job:     On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas,  employees were replacing insulators on shield wires above 500,000 volt transmission lines. Two of the employees had never worked on insulated shield wires before and did not know the hazards associated with the tasks. The employee in charge did not brief the employees on the presence of induced voltage or minimum approach distance, before the work commenced. This condition exposed the employees to electrocution hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.269 L01

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.269(l)(1): Unqualified employees were allowed to work on or with exposed energized lines or parts of equipment:   On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas, where employees were replacing insulators on shield wires above 500,000 volt transmission lines and equipment, unqualified employees were allowed to work on the shield wires with induced current present. This condition exposed employees to electrocution hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $7000

1910.269 L02

Serious Gravity 10 2 instances 4 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.269(l)(2): The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than set forth in Tables R-6 through R-10:     On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas, where employees were replacing insulators on shield wires above 500,000 volt transmission lines, the employees approached closer to energized parts than set forth in Table R-6, exposing employees to electrocution hazards in the following instances:     a) The shield wire on the north side of the lattice tower   b) The shield wire on the south side of the lattice tower
Recent events (2)
  • · I (S) $4900
  • · Z (S) $7000

1910.269 N05

Serious Gravity 10 2 instances 3 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $7,000 · Current $4,900 Reduced
29 CFR 1910.269(n)(5): Before any ground was installed, lines and equipment were not tested and found absent of nominal voltage, unless a previously installed ground was present.     On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas,  employees were replacing insulators on shield wires above 500,000 volt transmission lines. The employees did not test the ungrounded shield lines, for voltage, prior to installing the ground wires by hand. This condition exposed the employees to the hazard of electrocution in the following instances:     a) The shield wire on the north side of the lattice tower   b) The shield wire on the south side of the lattice tower
Recent events (2)
  • · I (S) $4900
  • · Z (S) $7000

1910.269 N06

Serious Gravity 10 2 instances 3 exposed
Issued
Feb 5, 2014
Abate by
Feb 13, 2014
Penalty
Initial $6,300 · Current $4,410 Reduced
29 CFR 1910.269(n)(6): When a ground was to be attached to a line or to equipment, the ground-end connection was attached first, and then the other end was not attached by means of a live-line tool.     On or about September 15, 2013, at the job site at or near Entergy tower 197, north of Alpine, Arkansas, employees were replacing insulators on shield wires above 500,000 volt transmission lines. The employees did not use live line tools to connect the grounds to the shield wires. The employees attached the ground wires, to the tower, and then to the shield wires, by hand. This condition exposed the employees to electrocution hazards in the following instances:     a)     The north side of the lattice tower   b)     The south side of the lattice tower
Recent events (2)
  • · I (S) $4410
  • · Z (S) $6300

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339415077.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.