Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: CAPITOL CONSTRUCTION AND MILLWORKS, INC.

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CAPITOL CONSTRUCTION AND MILLWORKS, INC. in 467 NORTH 90 WEST, BLACKFOOT, ID 83221 (NAICS 333210). OSHA activity number 339415531.

Watch Capitol Construction AND Millworks, INC. — free Get an email when a new federal OSHA severe-injury report for Capitol Construction AND Millworks, INC. is published. One employer, no account, unsubscribe in one click.
Site address
467 NORTH 90 WEST
City
BLACKFOOT
State
ID
ZIP
83221
Mailing
568 WEST 200 NORTH, BLACKFOOT, ID 83221
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333210
Employees
5
Ownership type
A

4 citations on file for this inspection.

1910.107 G02

Serious Gravity 1 1 instance 3 exposed
Issued
Penalty
Initial $1200.00 · Current $600.00 Reduced
29 CFR 1910.107(g)(2): All spraying areas were not kept as free from the accumulation of deposits of combustible residues as practical, with cleaning conducted daily if necessary:    a) Spray Room: On or about September 10, 2013 at at times prior thereto, the interior surfaces of the spray room were covered with excessive deposits of peeling paint residue.    NOTE: This item was observed corrected during the inspection.
Recent events (2)
  • — I (S) $600
  • — Z (S) $1200

1910.22 A02

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.22(a)(2):  The floor of every workroom was not be maintained in a clean and, so far as possible, a dry condition.   a) On or about September 10, 2013, in the workplace:  Wood dust accumulations over 3 inches were present adjacent to the CNC Router.  Note:  this item was abated during the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 I A

Other-than-serious 1 instance 3 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(i)[A]:  The depth of the working space in the direction of access to live parts was less than indicated in Table S-1.  Distances were measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed.   a) On or about September 10, 2013, Circuit Breaker Panels on Manufacturing Floor:  Access to enclosed circuit breakers and panels ranging from 110 to 480 Volts for the manufacuring floor was hindered by storage of material.  There was not 3 feet of clear distance in front of the panels.  Note: This item was abated during the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)[A]: Flexible cords and cables were used as a substitute for the fixed wiring of a structure.   a) On or about September 10, 2013, in the manufacturing area: A damaged extension cord was utilized to power a Le-Matic Portable Edgebander.   b) On or about September 10, 2013, in the manufacturing area: A damaged extension cord was utilized to power the exhaust ventilation for a table saw.  Note: This item was abated during the inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339415531.