OSHA Inspection: PACIFIC POWER ELECTRICAL CONTRACTING LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PACIFIC POWER ELECTRICAL CONTRACTING LLC in PEARL HARBOR NAVAL SHIPYARD DRYDOCK #4, PEARL HARBOR, HI 96860 (NAICS 238210). OSHA activity number 339419368.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pacific Power Electrical Contracting LLC for free Get an email when a new federal OSHA severe-injury report for Pacific Power Electrical Contracting LLC is published. One employer, no account, unsubscribe in one click.
Site address
PEARL HARBOR NAVAL SHIPYARD DRYDOCK #4
City
PEARL HARBOR
State
HI
ZIP
96860
Mailing
94 141 PUANANE LOOP, MILILANI, HI 96789
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
Private (A)

3 citations on file for this inspection.

1910.132 A

Serious Gravity 10 1 instance 2 exposed
Issued
Nov 14, 2013
Abate by
Nov 21, 2013
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.132(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, and protective shields and barriers, were not used when necessary whenever hazards capable of causing injury and impairment were encountered:      This violation occurred on September 13, 2013, at the East pump well of Dry Dock #4; where the employer did not select and ensure that employees use proper electrical personal protective ARC Flash equipment on live and/or potentially live equipment.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

1910.147 C04 I

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 14, 2013
Abate by
Nov 21, 2013
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees are engaged in the activities covered by this section.       This violation occurred on September 13, 2013, at the East pump well of Dry Dock #4; where the employer did not utilize procedures for the control of potentially hazardous energy when the Motor Control Center high voltage unit was re-energized.
Recent events (2)
  • · I (S) $1680
  • · Z (S) $2800

1910.147 E02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 14, 2013
Abate by
Nov 21, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.147(e)(2)(i): Before lockout or tagout devices were removed and energy was restored to the machine or equipment, authorized employees did not ensure that all employees had been safely positioned or removed from the work area:    This violation occurred on September 13, 2013, at the East pump well of Dry Dock #4; where the employer did not did not ensure that all employees had been safely positioned or removed from the work area before the Motor Control Center high voltage unit was re-energized.