Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,124Inspections Most recent open 2026-08-25 Last loaded 2026-08-28

OSHA Inspection: HAHNEMANN UNIVERSITY HOSPITAL

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HAHNEMANN UNIVERSITY HOSPITAL in 230 N. BROAD ST., PHILADELPHIA, PA 19102 (NAICS 622110). OSHA activity number 339437535.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hahnemann University Hospital for free Get an email when a new federal OSHA severe-injury report for Hahnemann University Hospital is published. One employer, no account, unsubscribe in one click.
Site address
230 N. BROAD ST.
City
PHILADELPHIA
State
PA
ZIP
19102
Mailing
230 N. BROAD ST., PHILADELPHIA, PA 19102
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
2800
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    a) 230 N. Broad St, Philadelphia, PA - 22nd Floor Substation - The energized 480 volt, 2500 amp circuit breaker was not used in accordance with its listing and labeling, the circuit breaker was set on the floor propped up on wooden blocks and not installed in a cabinet. This condition exposed the employees to an electrocution/shock hazard.This violation was observed on or about October22, 2013.    Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

1910.303 G02 I

Serious Gravity 10 1 instance 3 exposed
Issued
Mar 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:     a) 230 N. Broad St, Philadelphia, PA - 22nd Floor Substation  The energized 480 volt bus bar was not guarded against accidental contact by approved cabinets or other forms of approved enclosures, thus exposing the employees to a electrocution/shock hazard. This violation was observed on or about October 22, 2013.    Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

View Hahnemann University Hospital's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339437535.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.