PHILADELPHIA, PA ·
OSHA Inspection: HAHNEMANN UNIVERSITY HOSPITAL
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of HAHNEMANN UNIVERSITY HOSPITAL in 230 N. BROAD ST., PHILADELPHIA, PA 19102 (NAICS 622110). OSHA activity number 339437535.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HAHNEMANN UNIVERSITY HOSPITAL
- Site address
- 230 N. BROAD ST.
- City
- PHILADELPHIA
- State
- PA
- ZIP
- 19102
- Mailing
- 230 N. BROAD ST., PHILADELPHIA, PA 19102
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 2800
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1910.303 B02
- Issued
- Mar 14, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) 230 N. Broad St, Philadelphia, PA - 22nd Floor Substation - The energized 480 volt, 2500 amp circuit breaker was not used in accordance with its listing and labeling, the circuit breaker was set on the floor propped up on wooden blocks and not installed in a cabinet. This condition exposed the employees to an electrocution/shock hazard.This violation was observed on or about October22, 2013. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
1910.303 G02 I
- Issued
- Mar 14, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: a) 230 N. Broad St, Philadelphia, PA - 22nd Floor Substation The energized 480 volt bus bar was not guarded against accidental contact by approved cabinets or other forms of approved enclosures, thus exposing the employees to a electrocution/shock hazard. This violation was observed on or about October 22, 2013. Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
- · I (S) $3500
- · Z (S) $7000
More inspections at Hahnemann University Hospital