CHAMBERSBURG, PA —
OSHA Inspection: ICELAND INCORPORATED
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ICELAND INCORPORATED in 225 WEST VINE STREET, CHAMBERSBURG, PA 17201 (NAICS 493110). OSHA activity number 339457178.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ICELAND INCORPORATED
- Site address
- 225 WEST VINE STREET
- City
- CHAMBERSBURG
- State
- PA
- ZIP
- 17201
- Mailing
- 225 WEST VINE STREET, CHAMBERSBURG, PA 17201
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 35
- Ownership type
- A
Citations
9 citations on file for this inspection.
5(a)(1)
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $3,500 · Current $3,500
0170
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that caused or were likely to cause death or serious physical harm in that employees were exposed to inhalation hazards from a release of anhydrous ammonia. (a) 225 Vine Street, Chambersburg Pennsylvania - Employees worked in a refrigerated warehouse that maintains an ammonia system of approximately 5800 pounds. The employer had not developed an Inspection and Maintenance Program to assess the mechanical integrity of the ammonia refrigeration systems. Mechanical systems include but are not limited to compressors, pressure vessels, heat exchangers, pumps, valves, piping and alarm equipment, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
5(a)(1)
- Issued
- Apr 30, 2014
- Abate by
- Jun 30, 2014
- Penalty
- Initial $3,500 · Current $1,000 Reduced
0170
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that caused or were likely to cause death or serious physical harm in that employees were exposed to inhalation hazards from a release of anhydrous ammonia due to a lack of safety measures. (a) 225 West Vine Street Chambersburg Pennsylvania - The employer did not ensure that the doors to the machinery room were tightly sealed exposing employees to an ammonia inhalation hazard in the event of a leak, on or about October 30, 2013. (b) 225 West Vine Street Chambersburg Pennsylvania - The employer did not post outside the machinery room door, immediately adjacent to each door, emergency shutdown procedures including precautions to be observed in case of a breakdown or leak, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $1000
- — Z (S) $3500
1910.23 C01
- Issued
- Apr 30, 2014
- Penalty
- Initial $3,500 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: (a) Roof - An employee accessed the roof to work on the refrigration system. The employer did not ensure that the end of the roof was provided with a guard rail system, on or about October 31, 2013. No abatement certification or documentation required.
Recent events (2)
- — I (O) $2500
- — Z (S) $3500
1910.23 D01
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails: (a) Roof - An employee accessed refrigeration equipment using stairs that were not provided with a standard stair rail on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.147 C01
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: (a) 225 West Vine Street Chambersburg Pennsylvania - An employee works on such equipment as pumps and compressors. The employer did not develop an adequate energy control program that included energy control procedures and periodic inspection, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
1910.147 C04 I
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: (a) 225 West Vine Street Chambersburg Pennsylvania - An employee worked on such equipment as pumps and compressors which have two sources of energy such as electric and ammonia. The employer did not develop specific energy control procedures for equipment with multiple sources of energy, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C06 I
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct an annual or more frequent inspection of the energy control procedure to ensure that the procedure and requirements of this standard were followed: (a) 225 West Vine Street Chambersburg Pennsylvania - An employee worked on such equipment as pumps and compressors which have two sources of energy such as electric and ammonia. The employer did not conduct audits of employees and energy control procedures, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 G01
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $3,500 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: (a) 225 West Vine Street Chambersburg Pennsylvania - The employer did not provide training to employees on general principles of fire extinguisher use and the hazards involved with incipient stage firefighting, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $1000
- — Z (S) $3500
1910.1200 H03 I
- Issued
- Apr 30, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $3,500 · Current $3,500
General-duty citation text
29 CFR 1910.1200(h)(3)(i): The employee training did not include the methods and observations used to detect the presence or release of a hazardous chemical in the work area: (a) 225 West Vine Street Chambersburg Pennsylvania - The employer did not provided employees with training on the methods and observations used to detect the presence or release of ammonia, on or about October 30, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $3500
- — Z (S) $3500
More inspections at Iceland Incorporated
View Iceland Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339457178.