OSHA Inspection: ELECTRICAL SOLUTIONS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ELECTRICAL SOLUTIONS in 13501 RACEWAY DRIVE, NORTHLAKE, TX 76262 (NAICS 238210). OSHA activity number 339478901.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electrical Solutions — free Get an email when a new federal OSHA severe-injury report for Electrical Solutions is published. One employer, no account, unsubscribe in one click.
Site address
13501 RACEWAY DRIVE
City
NORTHLAKE
State
TX
ZIP
76262
Mailing
1113 WESTMINISTER DRIVE, WAXAHACHIE, TX 75165
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
13
Ownership type
A

4 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 2 instances 2 exposed
Issued
Nov 18, 2013
Abate by
Nov 26, 2013
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:   On or about November 7, 2013, and times prior thereto the employer did not ensure electrical equipment used at a commercial construction site was used as per the equipment's listed and labeling:  1. At the rear North East corner outside of the construction project a 120/208V 10 Gauge Romex Cord lying on the ground was utilized as an extension cord to supply electrical power to employees performing electrical installation work inside of the construction project .  2. At the rear North East corner outside of the construction project a 120/208V electrical cabinet used to supply electrical power and branch feeds electrical to employees was not provided with weather proofing or designed for outdoor use.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.403 E

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 18, 2013
Abate by
Dec 17, 2013
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1926.403(e): All splices and joints and free ends of conductors were not covered with insulation equivalent to that of the conductors or with an insulating device designed for the purpose:   On or about November 7, 2013, and times prior thereto, electrical tape was used to insulate splices on an electrical cable that provided 120 / 208 volt service to the site, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.404 B01 I

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 18, 2013
Abate by
Dec 17, 2013
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites:   On or about November 7, 2013 and times prior thereto, electrical equipment in use by employees was not provided with ground fault circuit interrupters, exposing the employees to electric shock hazards.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

1926.404 C01 II B

Serious Gravity 1 1 instance 2 exposed
Issued
Nov 18, 2013
Abate by
Dec 17, 2013
Penalty
Initial $1,200 · Current $720 Reduced
29 CFR 1926.404(c)(1)(ii)(B): Open conductors for branch circuit, feeder, and service conductors rated 600 volts, nominal, or less and run outdoors did not conform to the minimum clearance of 12 feet over areas subject to vehicular traffic other than trucks:  On or about November 7, 2013 and times prior thereto, a branch circuit feeder line, that was used to provide electrical power for employees performing electrical installation work inside of a commercial building, was lying on the ground exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $720
  • — Z (S) $1200

View Electrical Solutions's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339478901.