PEARL, MS —
OSHA Inspection: ADVANCE TOOL & DIE, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of ADVANCE TOOL & DIE, INC. in 2750 OLD BRANDON ROAD, PEARL, MS 39288 (NAICS 331221). OSHA activity number 339482358.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADVANCE TOOL & DIE, INC.
- Site address
- 2750 OLD BRANDON ROAD
- City
- PEARL
- State
- MS
- ZIP
- 39288
- Mailing
- P. O. BOX 5465, PEARL, MS 39288
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331221
- Employees
- 5
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.215 A04
- Issued
- Jan 14, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Work rest(s) shall be kept adjusted closely to the wheel with a maximum opening of one-eighth inch: (a) Shop Area - On or about November 6, 2013 the work rest on the Baldor bench grinder was 2 inches from the wheel.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
1910.215 B09
- Issued
- Jan 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the wheel periphery(s) and the adjustable tongue or the end of the safety peripheral member at the top shall never exceed one-fourth inch: (a) Shop - On or about November 6, 2013 a Baldor bench grinder did not have a tongue guard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jan 14, 2014
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. (a) North End of Shop - On or about November 6, 2013, the electrical box was not mounted.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.303 G02 I
- Issued
- Jan 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidentalcontact by use of approved cabinets or other forms of approved enclosures or by any of the following means: (a) North End of Shop - On or about November 6, 2013 the electrical box did not have a faceplate.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Jan 14, 2014
- Abate by
- Jan 22, 2014
- Penalty
- Initial $2,000 · Current $1,200 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: (a) East Wall - On or about November 6, 2014 electrical breaker boxes were not labeled.
Recent events (2)
- — I (S) $1200
- — Z (S) $2000
1910.303 G01
- Issued
- Jan 14, 2014
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. (a) North End - On or about November 6, 2013 the electrical panel was blocked by the storage of supplies and parts.
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.132 D02
- Issued
- Jan 14, 2014
- Abate by
- Jan 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2): The employer shall verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated; the person certifying that the evaluation has been performed; the date(s) of the hazard assessment; and, which identifies the document as a certification of hazard assessment. (a) Facility - On or abount November 6, 2013 the employer did not certify that a workplace hazard assessment had been performed.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 E01
- Issued
- Jan 14, 2014
- Abate by
- Jan 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): Employers shall develop, implement, and maintain at each workplace, a written hazard communication program which at least describes how the criteria specified in paragraphs (f), (g), and (h) of this section for labels and other forms of warning, safety data sheets, and employee information and training will be met, and which also includes the following: (a) Facility - On or about November 6, 2013 the employer had not developed and implemented a written hazard communication program for employees using chemicals, such as, propane, oxygen, etc.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 331221)
More inspections in MS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339482358.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.