DALLAS, TX —
OSHA Inspection: BUCKLEY OIL COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BUCKLEY OIL COMPANY in 1809 ROCK ISLAND STREET, DALLAS, TX 75207 (NAICS 324110). OSHA activity number 339483133.
Where did this inspection happen?
- Establishment
- BUCKLEY OIL COMPANY
- Site address
- 1809 ROCK ISLAND STREET
- City
- DALLAS
- State
- TX
- ZIP
- 75207
- Mailing
- 1809 ROCK ISLAND STREET, DALLAS, TX 75207
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 324110
- Employees
- 25
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.106 B02 II A
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.106(b)(2)(ii)(a): The distance between any two flammable liquid storage tanks was less than 3 feet: This violation was observed on or about November 18, 2013, in the tank farm areas; where the distance between tank number 53 that held W-F thinner and tank number 54 that held dry cleaning fluid was less than 1-inch.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.106 F06
- Issued
- Penalty
- Initial $2000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.106(f)(6): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were handled, drawn, or dispensed where flammable vapors may reach a source of ignition: This violation was discovered on or about January 14, 2014, in the tank farm areas; where the employer used a broken S.R. Browne aluminum grounding/bonding clamp to prevent static electricity when dispensing flammable liquids. The clamp was missing the contact point.
Recent events (2)
- — I (S) $0
- — Z (S) $2000
1910.132 A
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.132(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, and maintained in a sanitary and reliable condition wherever it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact: This violation was observed on or about October 31, 2013, in the filling area; where an employee operated a Toyota 7FGU25 powered industrial truck without using the seat belt and was exposed to struck-by, tip-over and caught-in-between hazards.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.132 A
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.132(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, and maintained in a sanitary and reliable condition wherever it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact: This violation was observed on or about November 18, 2013, in the filling area; where an employee transferred products which contained the substances heptane, isopropyl alcohol, and methanol, from a fifty-five gallon drum into secondary containers without wearing splash goggles, a face-shield or synthetic apron.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 C01
- Issued
- Abate by
- Penalty
- Initial $2000.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): The employer did not mount, locate and identify portable fire extinguishers so that they were readily accessible to employees without subjecting the employees to possible injury: This violation was observed on or about January 14, 2014, in the filling shed area; where an Amerex fire extinguisher was located behind the filling table and was not readily accessible for use without subjecting employees to injury.
Recent events (2)
- — I (S) $0
- — Z (S) $2000
1910.178 C02 IV
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $1400.00 Reduced
General-duty citation text
29 CFR 1910.178(c)(2)(iv): Power-operated industrial trucks other than those designated as DY, EE, or EX were used in locations where the hazardous liquids, vapors or gases were normally confined within closed containers or closed systems from which they could escape only in case of accidental rupture or breakdown of such containers or systems, or in the case of abnormal operation of equipment The employer did not ensure that powered industrial trucks designated as DY, EE, or EX were used at the fill station when filling and handling 55 gallon containers and 350/360 gallon totes of flammable liquids.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.307 D
- Issued
- Abate by
- Penalty
- Initial $2800.00 · Current $0.00 Reduced
General-duty citation text
29 CFR 1910.307(d): All conduits were not threaded and made wrench-tight: This violation was observed on or about November 18, 2013, in the above ground storage tank area 1809, adjacent to tank number eighty; where a 1-inch rigid electrical conduit was not threaded and made wrench-tight, exposing energized electrical conductors in areas where HM-acetone was stored.
Recent events (2)
- — I (S) $0
- — Z (S) $2800
More inspections in this industry (NAICS 324110)
TORRANCE, CA—2026-07-15
TORRANCE REFINING COMPANY LLC
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
EL SEGUNDO, CA—2026-06-30
CHEVRON U.S.A. INC.
TRAINER, PA—2026-06-26
MONROE ENERGY, LLC
RICHMOND, CA—2026-06-17
CHEVRON U.S.A. INC.
More inspections in TX
WICHITA FALLS, TX—2026-07-16
UNITED RENTALS, INC.
SAN MARCOS, TX—2026-07-16
CASA MECHANICAL SERVICES, LTD.
CLARKSVILLE, TX—2026-07-15
SEQUOIAS TREE EXPERT LLC
EL PASO, TX—2026-07-15
SURE STEEL
CORPUS CHRISTI, TX—2026-07-15
NORTH STAR ENERGY SOLUTIONS LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339483133.