Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-03

OSHA Inspection: AMRON

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of AMRON in 920 AMRON AVE, ANTIGO, WI 54409 (NAICS 332992). OSHA activity number 339486607.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Amron for free Get an email when a new federal OSHA severe-injury report for Amron is published. One employer, no account, unsubscribe in one click.
Establishment
AMRON
Site address
920 AMRON AVE
City
ANTIGO
State
WI
ZIP
54409
Mailing
920 AMRON AVE, ANTIGO, WI 54409
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332992
Employees
209
Ownership type
A

2 citations on file for this inspection.

1910.147 C04 II B

Serious Gravity 10 1 instance 15 exposed
Issued
Feb 19, 2014
Abate by
Mar 28, 2014
Penalty
Initial $6,300 · Current $4,410 Reduced
29 CFR 1910.147(c)(4)(ii)(B): The energy control procedure did not clearly and specifically specify procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy:    a) On or about October 15, 2013, specific procedural energy control steps were not developed and utilized to ensure employees performing energy control procedures were protected from hazardous energy sources.     Abatement Certification and Abatement Documentation Required.
Recent events (2)
  • · I (S) $4410
  • · Z (S) $6300

1910.147 D05 I

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 19, 2014
Abate by
Mar 28, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.147(d)(5)(i): All potentially hazardous stored or residual energy was not relieved, disconnected, restrained or otherwise rendered safe after the application of lockout or tagout devices to energy isolating devices:   a)    On or about October 15, 2013, a maintenance mechanic A did not relieve stored energy that had been trapped between the main steam line valve and the 25 mm line steam valve causing scalding water and steam to be released when the valve seal was broken by the employee.     Abatement Certification and Abatement Documentation Required.