SEATTLE, WA ·
OSHA Inspection: NATIONAL PARK SERVICE, COLUMBIA CASCADES LAND RESOURCES PROGRAM CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE, COLUMBIA CASCADES LAND RESOURCES PROGRAM CENTER in 168 S. JACKSON STREET, SEATTLE, WA 98104 (NAICS 712190). OSHA activity number 339487100.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 168 S. JACKSON STREET
- City
- SEATTLE
- State
- WA
- ZIP
- 98104
- Mailing
- 168 S. JACKSON STREET, SEATTLE, WA 98104
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 9
- Ownership type
- Federal government (D)
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Dec 6, 2013
- Abate by
- Jan 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Room 22; A white relocatable power tap was plugged into another white relocatable power tap, which powered a phone charger. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. (b) Room 23, a White relocatable power tap was plugged into another white relocatable power tap which powered a white heater which ran at 12.5 amps. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. (c) General Work Area; A Magic Chef refrigerator was plugged into a relocatable power tap. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. (d) South Central Work Area, South Window wall, 2nd workstation; A white relocatable power tap was plugged into another white relocatable power tap. An extension cord was plugged into another extension cord, which was then plugged into a relocatable power tap which powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards.
Recent events (1)
- · Z (S) $0
1910.37 B06
- Issued
- Dec 6, 2013
- Abate by
- Jan 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color: a) Hallway North side of building; The exit sign could not illuminate, exposing employees to possible delayed egress hazards.
Recent events (1)
- · Z (O) $0
1910.37 B07
- Issued
- Dec 6, 2013
- Abate by
- Jan 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(7): Each exit sign did not have the word "Exit" in plainly eligible letters not less that six inches (15.2 cm) high, with the principal strokes of the letters in the word "Exit" not less than three fourths of an inch (1.9 cm) wide: a) Hallway North side of building; The letters in the exit sign were smaller than the regulation required.
Recent events (1)
- · Z (O) $0
1910.157 E02
- Issued
- Dec 6, 2013
- Abate by
- Jan 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) The Ansul Sentry fire extinguisher located in the hallway, was not visually inspected monthly.