POTTSTOWN, PA ·
OSHA Inspection: CONTINENTAL CONCRETE PRODUCTS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of CONTINENTAL CONCRETE PRODUCTS, INC. in 1 SOUTH GROSSTOWN RD, POTTSTOWN, PA 19464 (NAICS 327390). OSHA activity number 339489429.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CONTINENTAL CONCRETE PRODUCTS, INC.
- Site address
- 1 SOUTH GROSSTOWN RD
- City
- POTTSTOWN
- State
- PA
- ZIP
- 19464
- Mailing
- 1 SOUTH GROSSTOWN RD, POTTSTOWN, PA 19464
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 327390
- Employees
- 41
- Ownership type
- Private (A)
Citations
10 citations on file for this inspection.
1910.147 C06 I
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $2,678 · Current $2,074 Reduced
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) Worksite - On or about November 14, 2013, the employer had not conducted a periodic inspection of the facility's energy control procedures at least annually.
Recent events (2)
- · I (S) $2074
- · Z (S) $2678
1910.147 C07 I A
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i)(A): Authorized employee(s) did not receive training in the recognition of applicable hazardous energy sources, the type and magnitude of the energy available in the workplace, and the methods and means necessary for energy isolation: a) Worksite - On or about November 14, 2013, the employer did not provide training to employees who are authorized to perform lockout / tagout energy isolation.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.147 C07 I B
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i)(B): Affected employees were not instructed in the purpose and use of the energy control procedure: a) Worksite - On or about November 14, 2013, affected employees were not instructed on the purpose and use of the energy control procedures developed by the employer.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.254 D09 III
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $2,142 · Current $0 Reduced
General-duty citation text
29 CFR 1910.254(d)(9)(iii): Cables with damaged insulation or exposed bare conductors were not replaced: a) Specialty Bay - On or about November 14, 2013, the ground cable on the Lincoln welder had damaged insulation and exposing the bare conductors. b) Weld Shop - On or about November 14, 2013, the ground cable on the Miller welder had damaged insulation which exposed the bare conductors.
Recent events (2)
- · I (S) $0
- · Z (S) $2142
1910.304 F01 VIII
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $2,142 · Current $2,142
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) Specialty Shop - On or about November 14, 2013, employees are using non-SWD rated circuit breakers to control fluorescent lightining.
Recent events (2)
- · I (S) $2142
- · Z (S) $2142
1910.303 F02
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident a) Specialty Shop - On or about November 14, 2013, 208 Volt, 3 phase, 4 wire switches were not marked as to their purpose.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 B01 II
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $2,142 · Current $2,142
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Specialty Shop - On or about November 14, 2013, an electrical cabinet had openings that were not effectively closed, exposing employees to electrical hazards of up to 208 volts..
Recent events (2)
- · I (S) $2142
- · Z (S) $2142
1910.305 G02 III
- Issued
- Jan 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Weld Shop - On or about November 14, 2013, an extension cord attachment plug was not provided adequate strain relief while plugged into a live electrical outlet.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.334 A02 II
- Issued
- Jan 28, 2014
- Penalty
- Initial $1,607 · Current $0 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service: a) Tool Closet - On or about November 14, 2013, a Hitachi DH45MR electric hammer drill had its protective sheathing torn from its flexible cord and was not taken out of service.
Recent events (2)
- · I (S) $0
- · Z (S) $1607
1910.1200 H01
- Issued
- Jan 28, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $2,142 · Current $2,142
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: a) Worksite - On or about November 14, 2013, employees have not been trained on the written Hazard Communication Program and the hazardous chemicals that they use in their work area.
Recent events (2)
- · I (S) $2142
- · Z (S) $2142
More inspections at Continental Concrete Products, INC.
View Continental Concrete Products, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 327390)
More inspections in PA
Source