WASHINGTON, DC —
OSHA Inspection: ALLIED BARTON SECURITY SERVICES
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ALLIED BARTON SECURITY SERVICES in 2400 EAST CAPITOL ST.,SE, WASHINGTON, DC 20003 (NAICS 561612). OSHA activity number 339491573.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALLIED BARTON SECURITY SERVICES
- Site address
- 2400 EAST CAPITOL ST.,SE
- City
- WASHINGTON
- State
- DC
- ZIP
- 20003
- Mailing
- 2034 EISENHOWER AVE. SUITE 140, ALEXANDRIA, VA 22314
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 561612
- Employees
- 1000
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Jan 24, 2014
- Abate by
- Jan 30, 2014
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Employees in the Lot#5 guard booth were exposed to electrical fire hazards due to daisy chained relocatable power taps, on or about 11/18/13. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.303 B07 IV
- Issued
- Jan 24, 2014
- Penalty
- Initial $7,000 · Current $4,500 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. a) Employees in lot #6 were exposed to corrosion on exposed electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. b) Employees in lot #7 were exposed to corrosion on exposed electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. c) Employees in lot #8 were exposed to corrosion on exposed electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13.
Recent events (2)
- — I (S) $4500
- — Z (S) $7000
1910.303 G02 I
- Issued
- Jan 24, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a) Employees in lot #5 were exposed to electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. b) Employees in lot #6 were exposed to electrical hazards due to exposed electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. c) Employees in lot #7 were exposed to electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. d) Employees in lot #8 were exposed to electrical connections in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 V
- Issued
- Jan 24, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(v): Employees did not wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion: a) Employees in lot #5 are exposed to electrical arc flash hazards due to exposed busbars and wires in the panel which houses the breakers for the parking lot lights and are provided no eye or face protection while entering these panels or switching the breakers, on or about 11/18/13. b) Employees in lot #6 are exposed to electrical arc flash hazards due to exposed busbars and wires in the panel which houses the breakers for the parking lot lights and are provided no eye or face protection while entering these panels or switching the breakers, on or about 11/18/13. c) Employees in lot #7 are exposed to electrical arc flash hazards due to exposed busbars and wires in the panel which houses the breakers for the parking lot lights and are provided no eye or face protection while entering these panels or switching the breakers, on or about 11/18/13. d) Employees in lot #8 are exposed to electrical arc flash hazards due to exposed busbars and wires in the panel which houses the breakers for the parking lot lights and are provided no eye or face protection while entering these panels or switching the breakers, on or about 11/18/13.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.332 B02
- Issued
- Jan 24, 2014
- Penalty
- Initial $3,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.332(b)(2): Employees, who were not qualified persons, were not trained in and familiar with any electrically related safety practices not specifically addressed by 29 CFR 1910.331 through 29 CFR 1910.335, but which were necessary for their safety: a) Employees in lot #5 were exposed to busbars and wires in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. b) Employees in lot #6 were exposed to busbars and wires in the panel which houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. c) Employees in lot #7 were exposed to busbars and wires in the panel that houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13. d) Employees in lot #8 were exposed to busbars and wires in the panel which houses the breakers for the parking lot lights and were provided no protection while entering these panels or switching the breakers, on or about 11/18/13.
Recent events (2)
- — I (S) $0
- — Z (S) $3000
1910.305 B02
- Issued
- Jan 24, 2014
- Penalty
- Initial $1,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) The outlet box in the guard booth in Lot #5 had no cover exposing employees to potential fire hazards, on or about 11/18/13. b) The outlet box in the guard booth in the office had no cover exposing employees to potential fire hazards, on or about 11/18/13. Allied Barton Security Services, Inc., was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(b)(2), which was contained in OSHA inspection number 315438838, citation number 1,item number 1 and was affirmed as a final order on 05/11/11, with respect to a workplace located at 135 Duffield Ave., Jersey City, NJ, 07306.
Recent events (2)
- — I (R) $0
- — Z (R) $1000
1910.157 C01
- Issued
- Jan 24, 2014
- Abate by
- Feb 5, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) The fire extinguisher located in the office was unmounted and free standing in the corner, on or about 11/18/13. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Allied Barton Security Services
View Allied Barton Security Services's full OSHA safety record →
More inspections in this industry (NAICS 561612)
More inspections in DC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339491573.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.