OSHA Inspection: RICHARDS BRICK COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RICHARDS BRICK COMPANY in 3816 NORTH UNION BOULEVARD, SAINT LOUIS, MO 63115 (NAICS 327120). OSHA activity number 339497638.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Richards Brick Company — free Get an email when a new federal OSHA severe-injury report for Richards Brick Company is published. One employer, no account, unsubscribe in one click.
Site address
3816 NORTH UNION BOULEVARD
City
SAINT LOUIS
State
MO
ZIP
63115
Mailing
3816 NORTH UNION BOULEVARD, SAINT LOUIS, MO 63115
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327120
Employees
11
Ownership type
A

3 citations on file for this inspection.

1910.304 G05

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 10, 2013
Abate by
Jan 7, 2014
Penalty
Initial $1,020 · Current $714 Reduced
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.  1. Inside of the employee trailer, employees were using a white Westinghouse microwave that was not grounded. The metal casing (framing) of the appliance was energized. The ground pin was missing from the plug of the electrical cord used to energize the appliance.
Recent events (2)
  • — I (S) $714
  • — Z (S) $1020

1910.305 B01 I

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 10, 2013
Abate by
Jan 7, 2014
Penalty
Initial $1,020 · Current $714 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed.  1. Inside of the employee trailer, there was a 120/240 volt electrical panel box with four (4) unused openings located inside of the breaker box. The openings were covered with black tape and employees were exposed to physical contact with live parts.
Recent events (2)
  • — I (S) $714
  • — Z (S) $1020

1910.305 B02

Other-than-serious 1 instance 2 exposed
Issued
Dec 10, 2013
Abate by
Jan 7, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: In completed installations each outlet box shall have a cover, faceplate, or fixture canopy:  1. Inside of the employee trailer, there was a cover missing from the breaker box used to provide electricity to the trailer. The breaker box was located on the west wall of the trailer and employees could make physical contact with breakers and live parts in the box because no cover was in place.