KANSAS CITY, MO ·
OSHA Inspection: GATEWAY PACKAGING CO.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of GATEWAY PACKAGING CO. in 5910 WINNER RD, KANSAS CITY, MO 64125 (NAICS 322222). OSHA activity number 339501579.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GATEWAY PACKAGING CO.
- Site address
- 5910 WINNER RD
- City
- KANSAS CITY
- State
- MO
- ZIP
- 64125
- Mailing
- 5910 WINNER RD, KANSAS CITY, MO 64125
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322222
- Employees
- 114
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.303 B07 I
- Issued
- Feb 11, 2014
- Penalty
- Initial $2,168 · Current $1,518 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. In the knife area, employees were exposed to a fire risk because an electrical junction box did not have all opening covered to include knock-out plugs located on the side of the box.
Recent events (2)
- · I (S) $1517.6
- · Z (S) $2168
1910.305 G01 IV A
- Issued
- Feb 11, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $2,550 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): As a substitute for the fixed wiring of a structure; In locations near the knife area, employees were exposed to a fire risk as result of flexible cords, and extention cords, which were either present, or connected in series, to provide electirical power to equipment which was utilized on a permanent basis and was not temporary in nature. Abatement note: Abatement certification is required for this item use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- · I (S) $1785
- · Z (S) $2550
1910.305 G01 IV D
- Issued
- Feb 11, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Where attached to building surfaces; In locations near the knife area, employees were exposed to a fire risk as result of flexible cords, and extention cords, which were attached to ceiling rafters and structural columns to provide electirical power to equipment which was utilized on a permanent basis and was not temporary in nature. Abatement note: Abatement certification is required for this item use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.