ROCHESTER, NY ·
OSHA Inspection: ATLANTIC PLYWOOD CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of ATLANTIC PLYWOOD CORPORATION in 1671 LYELL AVENUE, ROCHESTER, NY 14606 (NAICS 423310). OSHA activity number 339505562.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATLANTIC PLYWOOD CORPORATION
- Site address
- 1671 LYELL AVENUE
- City
- ROCHESTER
- State
- NY
- ZIP
- 14606
- Mailing
- 1671 LYELL AVENUE, ROCHESTER, NY 14606
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423310
- Employees
- 18
- Ownership type
- Private (A)
Citations
7 citations on file for this inspection.
1910.23 C01
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $4,500 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards ( Note: Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard. ) a) On or about 12/3/13 on the roof of the Flammable storage room; employees connecting and disconnecting large totes of glue are exposed to fall hazards of 10 feet when they are working at a distance of two to three feet from the unguarded edge. Abatement Documentation Required
Recent events (2)
- · I (S) $3000
- · Z (S) $4500
1910.106 D04 I
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $3,600 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(i): 29 CFR 1910.106(d)(4)(i) Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised sill or ramp at least 4 inches in height: a) On or about 12/03/13 in the flammable storage room; the door sills on the north and east exit doors of the flammable storage room ( measuring 24' x 28' x 10' ) and the south exit door from the Tint Room ( measuring 10' x 10' x 10' ) were at floor level. Abatement Certification Required
Recent events (2)
- · I (S) $2500
- · Z (S) $3600
1910.106 D04 IV
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $3,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(iv): The ventilating equipment and any lighting fixtures were not operated by the same switch located outside of the door. a) On or about 12/3/13 in the Flammable storage room; the ventilation for this storage area ( a mechanical fan ) was operated by a switched located outside on the south wall of the building at a height of approximately 10 feet, while the light switch to this room was located inside on a wall adjacent to the flammable storage room and not interconnected to the ventilation equipment for this area. Abatement Certification Required
Recent events (2)
- · I (S) $0
- · Z (S) $3600
1910.106 D04 IV
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.106(d)(4)(iv): Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour. a) On or about 12/3/13 in the Flammable storage room; the mechanical exhaust ventilation system installed for this storage room was switched on but not exhausting air and appeared to be operating in a slight negative pressure. Abatement Certification Required
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.106 E06 I
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $2,700 · Current $1,500 Reduced
General-duty citation text
29 CFR 1910.106(e)(6)(i): Adequate precautions were not taken to prevent the ignition of flammable vapors: a) On or about 12/3/13 in the flammable storage room; waste stain, paints, and lacquers ( flammable liquids ) were dumped into a metal waste drum located on the south east wall without the drum being grounded or the use of a bonding cable. Abatement Certification Required
Recent events (2)
- · I (S) $1500
- · Z (S) $2700
1910.305 G01 IV A
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $3,600 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about on the east side of the Flammable storage room; a cord set was run from the outlet on the south wall of the building and along the east wall of the flammable storage room to supply power to the panel saw located on the north east outside wall of the storage room. Abatement Certification Required
Recent events (2)
- · I (S) $2500
- · Z (S) $3600
1910.305 G02 III
- Issued
- Dec 13, 2013
- Abate by
- Jan 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) On or about 12/3/13 on the east side of the Flammable storage room; a cord set, run from the outlet on the south wall of the building along the east wall of the flammable storage room to supply power to the panel saw located on the north east outside wall of the storage room, had the insulation pulled away from the connections on the male and female ends and exposed conductors. Abatement Certification Required
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at Atlantic Plywood Corporation
View Atlantic Plywood Corporation's full OSHA safety record →
More inspections in this industry (NAICS 423310)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339505562.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.