VIDOR, TX —
OSHA Inspection: INDUSTRIAL SHEETMETAL & FABRICATORS, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of INDUSTRIAL SHEETMETAL & FABRICATORS, INC. in 2650 E FREEWAY, VIDOR, TX 77662 (NAICS 332312). OSHA activity number 339508392.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INDUSTRIAL SHEETMETAL & FABRICATORS, INC.
- Site address
- 2650 E FREEWAY
- City
- VIDOR
- State
- TX
- ZIP
- 77662
- Mailing
- 2650 E FREEWAY, VIDOR, TX 77662
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332312
- Employees
- 20
- Ownership type
- A
Citations
15 citations on file for this inspection.
1910.212 A01
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by rotating parts: a) In the Fabrication Shop, where the unused portion of the HEM Saw horizontal bandsaw was not guarded.
Recent events (2)
- — I (S) $1120
- — Z (S) $2800
1910.252 B02 III
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,100 · Current $840 Reduced
General-duty citation text
29 CFR 1910.252(b)(2)(iii): Workers and other persons adjacent to the welding area were not required to wear appropriate goggles to protect them from the rays when noncombustible or flameproof screens or shields were not used: a) In the Fabrication Shop, where employees were not protected from welding rays while other employees performed welding tasks on metal frames.
Recent events (2)
- — I (O) $840
- — Z (S) $2100
1910.253 B04 III
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a) On the exterior of the Fabrication Shop, oxygen and fuel gas cylinders were stored adjacent to one another.
Recent events (2)
- — I (O) $1120
- — Z (S) $2800
1910.303 B02
- Issued
- May 23, 2014
- Penalty
- Initial $2,100 · Current $840 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) In the rear of the fabrication shop, where a 100 foot flexible cord was supplying power to a blue plastic quad box receptacle. The blue plastic quad box receptacle was not mounted on a finished structure as specified by the listing and labeling.
Recent events (2)
- — I (O) $840
- — Z (S) $2100
1910.303 C03 I
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose: a) In the Welding Shop, where the conductors in the back of CBI arc welding machines, model CBI-400, serial HK296037 were spliced and not insulated. b) In the Fabrication Shop, where the conductors on the rear of the Miller arc welding machine connected to the press brake in front of the bay door were spliced and not insulated.
Recent events (2)
- — I (S) $1120
- — Z (S) $2800
1910.303 G01 II
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,100 · Current $840 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) In the Fabrication Shop, where there was not a three foot clearance around the circuit panels. b) In the Welding Shop, where there was not a three foot clearance around the circuit panels.
Recent events (2)
- — I (O) $840
- — Z (S) $2100
1910.304 A02
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity: a) On the exterior wall of the fabrication shop, where the conductors providing electricity to the receptacle had reverse polarity.
Recent events (2)
- — I (O) $1120
- — Z (S) $2800
1910.305 A02 X
- Issued
- May 23, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: a) In the rear of the fabrication shop, where a 100 foot flexible cord supplying power to a blue plastic quad box receptacle was run underneath the doorway.
Recent events (2)
- — I (O) $1120
- — Z (S) $2800
1910.305 B01 I
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a) In the Fabrication Shop, where the conductors entering the electrical panels on the east wall of the shop were not protected from abrasions.
Recent events (2)
- — I (S) $1120
- — Z (S) $2800
1910.305 B01 II
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) In the Fabrication Shop, where the unused openings in circuit panel K1-2 were not effectively closed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: a) In the rear of the Fabrication Shop, where the strain relief on flexible cord that connected the Miller Millermatic portable welding machine, serial number KH534836 to the power plug was disconnected.
Recent events (2)
- — I (O) $1120
- — Z (S) $2800
1910.306 D01
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,800 · Current $1,120 Reduced
General-duty citation text
29 CFR 1910.306(d)(1): A disconnecting means was not provided in the supply circuit for each motor generated arc welder: a) In the Welding Shop, where there was no disconnect installed on the CBI arc welding machines, model CBI-400, serial HK296037. b) In the Fabrication Shop, where there was no disconnect installed on the Miller arc welding machine connected to the press break in front of the bay door.
Recent events (2)
- — I (O) $1120
- — Z (S) $2800
1910.332 B01
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $4,900 · Current $1,960 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: a) In the Fabrication Shop, where an employee was permitted to run and install electrical wiring.
Recent events (2)
- — I (S) $1960
- — Z (S) $4900
1910.1200 H02 III
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $2,100 · Current $840 Reduced
General-duty citation text
29 CFR 1910.1200(h)(2)(iii): The employer did not provide information to the employees as to the location and availability of the written hazard communication program, and safety data sheets (SDSs) required by 29 CFR 1910.1200: a) In the Fabrication Shop, where employees were not informed of the location of the safety data sheets. Employees are exposed to hazardous chemical such as, but not limited to, welding fumes from welding electrodes.
Recent events (2)
- — I (O) $840
- — Z (S) $2100
1910.178 L06
- Issued
- May 23, 2014
- Abate by
- Jun 26, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): a) At the facility, where the employer did not ensure that forklift operators were certified to operate the Sky Trak forklift, model #10054, serial #11523.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Industrial Sheetmetal & Fabricators, INC.
View Industrial Sheetmetal & Fabricators, INC.'s full OSHA safety record →