OSHA Inspection: STEVEN ROSE DBA ICE EFFECTS

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of STEVEN ROSE DBA ICE EFFECTS in 83 EAST WATER STREET, ROCKLAND, MA 02370 (NAICS 312113). OSHA activity number 339531519.

Watch Steven Rose DBA ICE Effects — free Get an email when a new federal OSHA severe-injury report for Steven Rose DBA ICE Effects is published. One employer, no account, unsubscribe in one click.
Site address
83 EAST WATER STREET
City
ROCKLAND
State
MA
ZIP
02370
Mailing
83 EAST WATER STREET, ROCKLAND, MA 02370
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312113
Employees
4
Ownership type
A

4 citations on file for this inspection.

1910.219 D01

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1360.00 · Current $300.00 Reduced
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o    Shop: In going nip on the belts and pulleys were not guarded on the ice cutting saw.
Recent events (2)
  • — I (S) $300
  • — Z (S) $1360

1910.303 B02

Serious Gravity 1 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $1020.00 · Current $300.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    Shop: Power strips were not used as listed and labeled    a) Ice Sculpture Room:       1. A power strip was used as a hanging pendant      2. Two power strips used to power overhead lights were connected in a chain.    b) Ice Making Room: A power strip used for pumps was mounted to a post and used in place of fixed wiring.
Recent events (2)
  • — I (S) $300
  • — Z (S) $1020

1910.303 G02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Penalty
Initial $867.00 · Current $300.00 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets of other forms of approved enclosures, or other means listed under this provision:    Shop: A fuse opening was not covered exposing live electrical parts.
Recent events (2)
  • — I (S) $300
  • — Z (S) $867

1910.305 G02 II

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1020.00 · Current $300.00 Reduced
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap:    Ice Making: The power cord for the overhead crane was not continuos. Two sections of cord were spliced together.
Recent events (2)