OSHA Inspection: MARINE CORPS COMMUNITY SERVICES - MIRAMAR

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MARINE CORPS COMMUNITY SERVICES - MIRAMAR in MCAS MIRAMAR 45233 ANTERES DRIVE BLDG. 2760, SAN DIEGO, CA 92145 (NAICS 452111). OSHA activity number 339533986.

Watch Marine Corps Community Services - Miramar — free Get an email when a new federal OSHA severe-injury report for Marine Corps Community Services - Miramar is published. One employer, no account, unsubscribe in one click.
Site address
MCAS MIRAMAR 45233 ANTERES DRIVE BLDG. 2760
City
SAN DIEGO
State
CA
ZIP
92145
Mailing
P.O. BOX 452008 MCCS DEPT, SAN DIEGO, CA 92145
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
452111
Employees
200
Ownership type
D

11 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 35 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:   Warehouse: On or about 23DEC13, boxes and merchandise carts were placed in the aisles of the warehouse restricting the exit routes.
Recent events (1)
  • — Z (S) $0

1910.178 L06

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
The employer did not certify that each operator had been trained and evaluated as required by this paragraph (l):   Warehouse: On or about 23DEC13, the employer failed to certify the training and evaluation of the employees operating powered industrial vehicles, where an electric pallet jack was provided for employee use without certifying the successful evaluation of training.
Recent events (1)
  • — Z (S) $0

1910.178 Q07

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.178(q)(7): Industrial trucks were not examined before being placed in service:   Warehouse: On or about 23DEC13, employees were not required to examine the electric pallet jack prior to use.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Warehouse: On or about 23DEC13, the employer provided a custom made flexible cord set with an electrical receptacle box designed for attachment to building surfaces as a method for providing 120VAC service.
Recent events (1)
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  Warehouse: On or about 23DEC13, 120VAC live conductors were exposed to inadvertent employee contact where an opening on an electrical box was left uncovered.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 5 1 instance 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Warehouse: On or about 23DEC13, the space before a single throw knife switch electrical box had a box of fishing poles stored immediately in front of it.
Recent events (1)
  • — Z (S) $0

1910.305 D02

Serious Gravity 5 2 instances 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(d)(2): Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons.  (a) Warehouse: On or about 23DEC13, a panelboard board cover was bent at the edges exposing the live conductors within to inadvertent contact by employees.  (b) Warehouse: On or about 23DEC13, two panelboard board covers had missing key tumblers in the latches leavings an opening in the front of the panel.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV

Serious Gravity 5 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):  (a) Warehouse, second floor electronics area: On or about 23DEC13, flexible cords were attached and run over the steel merchandise racks.  (b) Electronics, TV wall hallway: On or about 24DEC13, power strips were attached to the wall.   (c) Seasonal department: On or about 24DEC13, a flexible cord was run through openings in the ceiling. Exposure to electrical shock.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 3 instances 15 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  (a) Electronics service counter: On or about 24DEC13, exposed conductors were not provided protection from a pull being directly transmitted to joints or terminal screws where the sheathing of a flexible cord was pulled back from the connection plug.  (b) Electronics TV display: On or about 24DEC13, exposed conductors were not provided protection from a pull being directly transmitted to joints or terminal screws where the sheathing of a flexible cord was pulled back from the connection plug.  (c) Electronics TV wall hallway: On or about 24DEC13, exposed conductors were not provided protection from a pull being directly transmitted to joints or terminal screws where the sheathing of a flexible cord was pulled back from the connection plug.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Repeat Gravity 5 7 instances 35 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Warehouse: On or about 23DEC13, two power strips were connected in series to provide electrical service to device charging units.  (b) Warehouse, second floor: On or about 23DEC13, two extension cords connected in series to provide electrical service to an employees desk.  (c) Warehouse, second floor: On or about 23DEC13, two extension cords connected in series to provide electrical service to a pedestal fan.  (d) Warehouse, second floor: On or about 23DEC13, an extension cord and power strip were connected in series to provide electrical service to an employees desk.  (e) Electronics: On or about 24DEC13, an extension cord and power strip were connected in series to provide electrical service to display electronics.  (f) Electronics: On or about 24DEC13, two power strips were connected in series to provide electrical service to display electronics.  (g) Electronics: On or about 24DEC13, two power strips were connected in series to provide electrical service to display electronics.   The Marine Corps Community Services was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 281063, citation number 1, item number 3, and was affirmed as a final order on May 17, 2012, with respect to a workplace located at 45233 Anteres Drive, Bldg. 2760 & Camp Elliot, San Diego, CA 92145.
Recent events (1)
  • — Z (R) $0

1910.334 A02 II

Repeat Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.  Warehouse: On or about 23DEC13, a flexible cord in use had black tape covering damage to the insulation exposing employees to electrical shock.  The Marine Corps Community Services was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.334(a)(2)(ii), which was contained in OSHA inspection number 281063, citation number 1, item number 5, and was affirmed as a final order on May 17, 2012, with respect to a workplace located at 45233 Anteres Drive, Bldg. 2760 & Camp Elliot, San Diego, CA 92145.
Recent events (1)
  • — Z (R) $0