LANCASTER, PA ·
OSHA Inspection: ATT SPORTS INC.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of ATT SPORTS INC. in 1175 MANHEIM PIKE, LANCASTER, PA 17601 (NAICS 238990). OSHA activity number 339534422.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ATT SPORTS INC.
- Site address
- 1175 MANHEIM PIKE
- City
- LANCASTER
- State
- PA
- ZIP
- 17601
- Mailing
- 115 CROSS KEYS ROAD, BERLIN, NJ 08009
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238990
- Employees
- 6
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.404 B01 II
- Issued
- Jan 15, 2014
- Abate by
- Feb 11, 2014
- Penalty
- Initial $2,100 · Current $1,260 Reduced
General-duty citation text
29 CFR 1926.404(b)(1)(ii): Receptacles on a three-wire, dual voltage portable or vehicle-mounted generator rated at 5kW or more, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, were not be protected with ground-fault circuit interrupters. (a) Mosa Generator Serial Number 0000021255 - Employees used the three phase generator with no GFCI protection to provide power to the Plano Matic P703 paving machine. Employees operated the paving pachine to smooth out the polyurethane binder and rubberized granules for the field hockey pitch and were exposed to the hazards of electrical shock on or about December 27, 2013. (b) Olympian Generator Serial Number oly00000EGEL00369 - Employees used the three phase generator with no GFCI protection to provide power to the SMG M 6004S Mix Matic mixer. Employees operated the mixer to combine the polyurethane binder and rubberized granules for the field hockey pitch and were exposed to the hazards of electrical shock on or about December 27, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- · I (S) $1260
- · Z (S) $2100
1926.403 G
- Issued
- Jan 15, 2014
- Abate by
- Feb 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(g): Electrical equipment which was used did not have other markings giving voltage, current, wattage, or other ratings as necessary: (a) Olympian Generator - The employer used the generator to provide power to the SMG M6004S Mix Matic. The employer did not ensure that durable markings giving the voltage, current, wattage or other ratings were affixed to the generator on or about December 27, 2013. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- · I (O) $0
- · Z (O) $0
More inspections in this industry (NAICS 238990)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339534422.