HURON, SD ·
OSHA Inspection: OVERBUILT, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of OVERBUILT, INC. in 780 WESTPARK AVENUE, HURON, SD 57350 (NAICS 333120). OSHA activity number 339537094.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OVERBUILT, INC.
- Site address
- 780 WESTPARK AVENUE
- City
- HURON
- State
- SD
- ZIP
- 57350
- Mailing
- 780 WESTPARK AVENUE, HURON, SD 57350
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333120
- Employees
- 52
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.212 A03 II
- Issued
- Apr 30, 2014
- Abate by
- May 30, 2014
- Penalty
- Initial $2,100 · Current $1,470 Reduced
General-duty citation text
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle: (a) On or about December 18, 2013 and at times prior to that date, for employees exposed to amputation hazards where a Parker crimping machine, model no.TH8-D206 was operated in the fabrication area without barrier guarding at 780 Westpark Avenue, Huron, South Dakota.
Recent events (2)
- · I (S) $1470
- · Z (S) $2100
1910.303 B02
- Issued
- Apr 30, 2014
- Abate by
- May 12, 2014
- Penalty
- Initial $2,100 · Current $1,470 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) On or about December 18, 2013 and at times prior to that date, for employees exposed to electrical hazards where an electrical power strip was series-connected to an extension cord while providing electrical power to a space heater and drill press at 780 Westpark Avenue, Huron, South Dakota.
Recent events (2)
- · I (S) $1470
- · Z (S) $2100
1910.303 G02 I
- Issued
- Apr 30, 2014
- Abate by
- May 12, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures: (a) On or about December 18, 2013 and at times prior to that date, for employees exposed to electrical hazards where electrical wires from the furnace Dayton speed control were exposed at 780 Westpark Avenue, Huron, South Dakota. (b) On or about December 18, 2013 and at times prior to that date, for employees exposed to electrical hazards where electrical wires from the furnace motorized pump assembly were exposed at 780 Westpark Avenue, Huron, South Dakota.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.304 B02
- Issued
- Apr 30, 2014
- Abate by
- May 12, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(2): Outlet devices had an ampere rating less than the load being served: (a) On or about December 18, 2013 and at times prior to that date, for employees exposed to electrical hazards where a space heater and drill press received electrical power while plugged into a power strip at 780 Westpark Avenue, Huron, South Dakota.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 A02 IX
- Issued
- Apr 30, 2014
- Abate by
- May 12, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lamp holder with a guard: (a) On or about December 18, 2013 and at times prior to that date, for employees exposed to struck-by hazards where a florescent lamp fixture was located directly above a maintenance workstation at 780 Westpark Avenue, Huron, South Dakota.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at Overbuilt, INC.
View Overbuilt, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 333120)
More inspections in SD
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339537094.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.