Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCHONE INDUSTRIES INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MCHONE INDUSTRIES INC in 110 ELM STREET, SALAMANCA, NY 14779 (NAICS 333999). OSHA activity number 339548539.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mchone Industries INC — free Get an email when a new federal OSHA severe-injury report for Mchone Industries INC is published. One employer, no account, unsubscribe in one click.
Site address
110 ELM STREET
City
SALAMANCA
State
NY
ZIP
14779
Mailing
110 ELM STREET, SALAMANCA, NY 14779
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333999
Employees
84
Ownership type
A

3 citations on file for this inspection.

1910.36 A02

Serious Gravity 1 1 instance 9 exposed
Issued
Jul 9, 2014
Abate by
Aug 21, 2014
Penalty
Initial $1,785 · Current $1,339 Reduced
29 CFR 1910.36(a)(2): An exit must be separated by fire resistant materials. Construction materials used to separate an exit from other parts of the workplace must have a one-hour fire resistance-rating if the exit connects three or fewer stories and a two-hour fire resistance-rating if the exit connects four or more stories.  a) On or about 4/24/14, front stairwell exit did not meet the one-hour fire resistance rating due to numerous penetrations in the walls and ceiling.  Abatement Certification Required:
Recent events (2)
  • — I (S) $1338.75
  • — Z (S) $1785

1910.22 D01

Other-than-serious 1 instance 1 exposed
Issued
Jul 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): In every building or other structure, or part thereof, used for mercantile, business, industrial, or storage purposes, the loads approved by the building official shall be marked on plates of approved design which shall be supplied and securely affixed by the owner of the building, or his duly authorized agent, in a conspicuous place in each space to which they relate. Such plates shall not be removed or defaced but, if lost, removed, or defaced, shall be replaced by the owner or his agent.  a) On or about 4/24/14, mezzanine that was use as storage for boxes business records, did not have a load capacity plate.  No Abatement Required:
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.37 B06

Other-than-serious 1 instance 9 exposed
Issued
Jul 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 foot lamberts (0.21 cd/m2) are permitted.  a) On or about 4/24/14 in the shipping area, exit sign above the exit door was not illuminated making it difficult to see in the darken hallway.  No Abatement Required:
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Mchone Industries INC's full OSHA safety record →