SIKESTON, MO ·
OSHA Inspection: SABONA OF LONDON, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SABONA OF LONDON, INC. in 609 DAVIS BOULEVARD, SIKESTON, MO 63801 (NAICS 331420). OSHA activity number 339548737.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SABONA OF LONDON, INC.
- Site address
- 609 DAVIS BOULEVARD
- City
- SIKESTON
- State
- MO
- ZIP
- 63801
- Mailing
- 609 DAVIS BOULEVARD, SIKESTON, MO 63801
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331420
- Employees
- 12
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.305 B01 I
- Issued
- Jan 28, 2014
- Penalty
- Initial $1,700 · Current $1,190 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:(a) (LOCATION) (IDENTIFY EQUIPMENT AND CONDITION(S)) (STATE HAZARD(S) TO EMPLOYEE(S)) 1. On the west wall, behind the packaging area, there was a 110/220 volt panel box with four (4) unused openings located inside of the breaker box. Employees were exposed to contact with live parts.
Recent events (2)
- · I (S) $1190
- · Z (S) $1700
1910.303 F
- Issued
- Jan 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:(a) (LOCATION) (IDENTIFY EQUIPMENT) (STATE HAZARD(S) TO EMPLOYEE(S)) 1. Inside of the break area, on the south wall, there was a 110/220 volt panel box that was not marked to indicate the purpose of each breaker contained inside of the box. There was no circuit directory inside of the breaker box. 2. Inside of the file storage room, on the west wall, there was a 110/220 volt panel box with no circuit directory (ledger)located inside of the box. 3. On the west wall, behind the packaging area, there was a large 110/220 volt panel box with no circuit directory (ledger) located inside of the breaker box. 4. On the west wall, behind the packaging area, there was a small 110/220 volt panel box with no circuit directory (ledger) located inside of the panel box.
Recent events (2)
- · I (O) $0
- · Z (O) $0
1910.305 B02
- Issued
- Jan 28, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:(a)(LOCATION)(IDENTIFY EQUIPMENT AND CONDITION(S))(STATE HAZARD(S) TO EMPLOYEE(S)) 1. Inside of the file storage room, on the west wall, there were two (2) knockouts missing from the side of the 110/220 volt panel box.
Recent events (2)
- · I (O) $0
- · Z (O) $0