Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: AOTCO METAL FINISHING, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AOTCO METAL FINISHING, INC. in 11 SUBURBAN PARK DRIVE, BILLERICA, MA 01821 (NAICS 332813). OSHA activity number 339550022.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Aotco Metal Finishing, INC. for free Get an email when a new federal OSHA severe-injury report for Aotco Metal Finishing, INC. is published. One employer, no account, unsubscribe in one click.
Site address
11 SUBURBAN PARK DRIVE
City
BILLERICA
State
MA
ZIP
01821
Mailing
11 SUBURBAN PARK DRIVE, BILLERICA, MA 01821
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
43
Ownership type
A

5 citations on file for this inspection.

1910.106 D04 I

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 7, 2014
Abate by
Apr 21, 2014
Penalty
Initial $4,900 · Current $2,450 Reduced
29 CFR 1910.106(d)(4)(i): Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid tight raised seal or ramp at least 4 inches in height. Opening(s) from inside flammable and combustible storage room(s) were not provided with approved self-closing fire doors. The inside flammable and combustible storage room(s) were not liquid-tight where the walls joined the floor:    (a) Location - 11 Suburban Park Drive, Billerica, MA:    On or about 1/16/2014, the facilities inside storage room for flammable and combustible liquids was not equipped with a liquid-tight seal or ramp at least four inches in at height at its opening, was not equipped with a self-closing fire door, and was not liquid tight where the walls joined the floor.
Recent events (2)
  • · I (S) $2450
  • · Z (S) $4900

1910.106 D04 III

Serious Gravity 5 1 instance 4 exposed
Issued
Feb 7, 2014
Abate by
Apr 21, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(iii): Wiring. Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use:    (a) Location - 11 Suburban Park Drive, Billerica, MA:    On or about 1/16/2014, the light fixture in the facility's inside storage room for flammable and combustible liquids was not approved for Class I Division 2 Hazardous Locations.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.106 D04 IV

Serious Gravity 5 1 instance 4 exposed
Issued
Feb 7, 2014
Abate by
Apr 21, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.106(d)(4)(iv): Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour.     (a) Location - 11 Suburban Park Drive, Billerica, MA:    On or about 1/16/2014, the facility's inside storage room for flammable and combustible liquids was not provided gravity or mechanical exhaust ventilation.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.147 C07 I B

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 7, 2014
Abate by
Mar 14, 2014
Penalty
Initial $2,625 · Current $1,215 Reduced
29 CFR 1910.147(c)(7)(i)(B): Affected employees were not instructed in the purpose and use of the energy control procedure:    (a) Location - 11 Suburban Park Drive, Billerica, MA:    On or about 1/16/2014, production employees who work in areas within the facility with machines capable of being locked and tagged out have not been given training in the purpose and use of hazardous energy control procedures.
Recent events (2)
  • · I (S) $1215
  • · Z (S) $2625

1910.1027 K01

Other-than-serious 1 instance 1 exposed
Issued
Feb 7, 2014
Abate by
Mar 14, 2014
Penalty
Initial $0 · Current $0

Hazardous substances C141

29 CFR 1910.1027(k)(1): Surfaces were not maintained as free as practicable of accumulations of cadmium:  (a) Location - 11 Suburban Park Drive, Billerica, MA:  On or about 1/16/2014, the level of cadmium surface contamination on the counter of a dip tank used in cadmium plating processes was excessive.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339550022.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.