Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCCOLLISTER'S TRANSPORTATION SYSTEMS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MCCOLLISTER'S TRANSPORTATION SYSTEMS, INC. in 2760 PACIFIC DRIVE, NORCROSS, GA 30071 (NAICS 531120). OSHA activity number 339559650.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mccollister'S Transportation Systems, INC. — free Get an email when a new federal OSHA severe-injury report for Mccollister'S Transportation Systems, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2760 PACIFIC DRIVE
City
NORCROSS
State
GA
ZIP
30071
Mailing
2760 PACIFIC DRIVE, NORCROSS, GA 30071
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
531120
Employees
1000
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 11, 2014
Abate by
Mar 17, 2014
Penalty
Initial $2,250 · Current $1,350 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about 1/23/2014 at 2760 Pacific Drive, Norcross, GA; employees were exposed to electrical shock and burn hazards where a metallic quad receptacle was improperly used as a pendant. Employees last used the pendant in November, 2013 for one full 8-10 hour shift to power battery charging stations for cordless drills.
Recent events (2)
  • — I (S) $1350
  • — Z (S) $2250

1910.305 G02 III

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 11, 2014
Abate by
Mar 17, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  On or about 1/23/2014 at 2760 Pacific Drive, Norcross, GA; employees were exposed to electrical shock and burn hazards where a metallic quad receptacle was improperly used as a pendant and strain relief was not effective. Employees last used the pendant in November, 2013 for one full 8-10 hour shift to power battery charging stations for cordless drills.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 1 3 instances 32 exposed
Issued
Mar 11, 2014
Abate by
Apr 13, 2014
Penalty
Initial $2,250 · Current $1,350 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  On or about 1/23/2014 at 2760 Pacific Drive, Norcross, GA; employees were exposed to electrical shock and burn hazards where:  A. A metallic box housing a snap switch that controlled the wall fan on the back wall, was missing a knock out; B. A metallic box housing a dual electrical outlet used for a mounted fan was damaged, exposing the live parts inside; and  C. A metallic box housing a dual electrical outlet used for a mounted fan was damaged, exposing the live parts inside.
Recent events (2)
  • — I (S) $1350
  • — Z (S) $2250

1910.157 E02

Other-than-serious 1 instance 32 exposed
Issued
Mar 11, 2014
Abate by
Apr 13, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  On or about 1/23/2014 at 2760 Pacific Drive, Norcross, GA; where employees are expected to fight small fires, the portable fire extinguishers had not been inspected since 10/22/2013.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 G01

Other-than-serious Gravity 1 1 instance 1 exposed
Issued
Mar 11, 2014
Abate by
Apr 13, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting:  On or about 1/23/2014 at 2760 Pacific Drive, Norcross, GA; employees that are expected to fight small fires are not trained.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Mccollister'S Transportation Systems, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339559650.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.