Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VISUAL PRODUCTS CORP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VISUAL PRODUCTS CORP in 2930 W. 9TH AVE., DENVER, CO 80204 (NAICS 339950). OSHA activity number 339566622.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Visual Products Corp — free Get an email when a new federal OSHA severe-injury report for Visual Products Corp is published. One employer, no account, unsubscribe in one click.
Site address
2930 W. 9TH AVE.
City
DENVER
State
CO
ZIP
80204
Mailing
P.O. BOX 4311, DENVER, CO 80204
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339950
Employees
44
Ownership type
A

9 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that employees were protected from rotating parts in the following instances:        1)  A Jet horizontal bandsaw, serial number WJ00311-OCP, used to cut steel and aluminum, was missing guards on both sides of the non-working parts of the blade, including 7 inches on one side and 4 inches on the other side; and            2)  A Delta vertical bandsaw was missing a guard over the upper non-working part of the blade measuring 2 inches.     Conditions exposed employees to amputation hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3400

1910.212 A05

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch:  a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that three 16 inch round fans in the compressor room, located 75 inches above the floor, were guarded.  Condition exposed employees to amputation hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 B

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that the air nozzles used to blow off sanding dust in the paint area included side discharge nozzles to reduce the compressed air to less than 30 psi.  Conditions exposed employees who sand and paint to soft tissue damage and embolisms.
Recent events (2)
  • — I (S) $1275
  • — Z (S) $2550

1910.305 B01 I

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed:     a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that an opening in the compressor breaker panel for the conduit, in the compressor room, was closed.  Condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3400

1910.305 C04

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(c)(4):  Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:  a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that two switches in the compressor room, used to control a 120 volt fan and a light, included faceplates.  Condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 I

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:  a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer allowed employees to use a receptacle in the compressor room that was less than 8 feet high and was missing a faceplate.  Condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.307 C03

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 14, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c)(3): Equipment was not safe for the location in that it was not of a type and design that the employer demonstrated would provide protection from the hazards arising from the combustibility and flammability of vapors, liquids, gases, dusts, or fibers involved:  a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that a receptacle box was safe for the location in that it were not covered, and was not intrinsically safe, located near the corner of a paint booth wall, and near a mixing container that was used to mix flammable and combustible paint.  Condition exposed employees to explosion hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E02 II

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 14, 2014
Abate by
Aug 7, 2014
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.106(e)(2)(ii): 29 CFR 1910.106(e)(2)(ii):  Flammable or combustible liquids were not stored in tanks or closed containers:    a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer stored waste flammable and combustible liquids in a 55 gallon barrel with a funnel in an open bung.  Condition exposed employees to fire and explosion hazards.
Recent events (2)
  • — I (S) $1275
  • — Z (S) $2550

1910.107 E09

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 14, 2014
Abate by
Aug 7, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.107(e)(9): 29 CFR 1910.107(e)(9):  Flammable liquids for use in spraying operations were transferred from one container to another without both containers being effectively bonded and grounded to prevent discharge sparks of static electricity.  a)  Visual Products Corp at 2930 W. 9th Ave., Denver, CO 80204:  On or before January 29, 2014, the employer did not ensure that metal containers were bonded and grounded when pouring flammable and combustible lacquer and paints into a metal 55 gallon storage drum.  Condition exposed employees to explosion hazards from static electricity.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Visual Products Corp's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339566622.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.