Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: REDDY ICE CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of REDDY ICE CORPORATION in 624 MORENO STREET, GAINESVILLE, GA 30501 (NAICS 312113). OSHA activity number 339567281.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Reddy ICE Corporation — free Get an email when a new federal OSHA severe-injury report for Reddy ICE Corporation is published. One employer, no account, unsubscribe in one click.
Site address
624 MORENO STREET
City
GAINESVILLE
State
GA
ZIP
30501
Mailing
624 MORENO STREET, GAINESVILLE, GA 30501
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
312113
Employees
14
Ownership type
A

3 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 4, 2014
Abate by
Mar 28, 2014
Penalty
Initial $3,825 · Current $3,825
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employement and a place of employement which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees, in that employees were exposed to ammonia releases and exposures.   On or about 1/28/14, at the Gainesville Georgia facility, employees were exposed to ammonia hazards as the employer did not ensure the Ammonia machinery room was equipped with tight fitting doors that led into the production area.    This hazard is recognized in safety documents: ANSI/IIAR 2-2008, Equipment, Design and Installation of Closed Circuit Ammonia Mechanical Refrigeration Systems, 13.3.3 Access and Egress.
Recent events (2)
  • — I (S) $3825
  • — Z (S) $3825

1910.36 D01

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Mar 4, 2014
Abate by
Mar 28, 2014
Penalty
Initial $3,825 · Current $0 Reduced
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge.  On or about 1/28/14, at the Gainesville Ga facility, the exit door in the ammonia engine room was equipped with a dead bolt lock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3825

1910.37 B02

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Mar 4, 2014
Abate by
Mar 28, 2014
Penalty
Initial $3,825 · Current $0 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit".  On or about 1/28/14, at the Gainesville Ga. facility, in the Ammonia engine room the designated exit door was marked "Not an Exit".
Recent events (2)
  • — I (S) $0
  • — Z (S) $3825

View Reddy ICE Corporation's full OSHA safety record →