OSHA Inspection: PROFILES IN DESIGN, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PROFILES IN DESIGN, LLC in 860 DELLWAY, CINCINNATI, OH 45229 (NAICS 337110). OSHA activity number 339567331.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Profiles in Design, LLC for free Get an email when a new federal OSHA severe-injury report for Profiles in Design, LLC is published. One employer, no account, unsubscribe in one click.
Site address
860 DELLWAY
City
CINCINNATI
State
OH
ZIP
45229
Mailing
860 DELLWAY, CINCINNATI, OH 45229
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
10
Ownership type
A

5 citations on file for this inspection.

1910.178 L01 I

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 27, 2014
Abate by
May 23, 2014
Penalty
Initial $1,200 · Current $500 Reduced
29 CFR 1910.178(l)(1)(i): The employer shall ensure that each powered industrial truck operator is competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l).      a) The employer did not ensure that the forklift operators were trained in the elements of video and/or written training material(s), test of knowledge received and hands on evaluation prior to allowing them to operate a powered industrial lift truck.
Recent events (2)
  • · I (S) $500
  • · Z (S) $1200

1910.212 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 27, 2014
Abate by
May 23, 2014
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.212(a)(1): Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are-barrier guards, two-hand tripping devices,electronic safety devices, etc.    a) Machine guarding was not provided on the Achilles model MBS-3000CE Bridge Saw  to prevent employees exposure to pinch points created as the cutting head moves.
Recent events (2)
  • · I (S) $1400
  • · Z (S) $2800

1910.303 G02 II

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 27, 2014
Abate by
Apr 22, 2014
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage.    a) The enclosure for the control panel was not secured in place to prevent operators from opening it, on the granite cutting machine Mfr # MBS 3000.
Recent events (2)
  • · I (S) $1400
  • · Z (S) $2800

1910.305 G01 I

Other-than-serious 1 instance 1 exposed
Issued
Mar 27, 2014
Abate by
Apr 8, 2014
Penalty
Initial $1,600 · Current $0 Reduced
29 CFR 1910.305(g)(1)(i): Flexible cords and cables shall be approved for conditions of use and location.      a) Drop cord in the finishing department was not approved for the location in that the cord was being used in a wet location and had electrical tape covering the connectors.
Recent events (2)
  • · I (O) $0
  • · Z (S) $1600

1910.305 C04

Serious Gravity 1 1 instance 1 exposed
Issued
Mar 27, 2014
Abate by
Apr 3, 2014
Penalty
Initial $1,200 · Current $200 Reduced
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.    a) Electrical light switch in the mens room did not have a cover to prevent employees from contact.