CARNEGIE, PA —
OSHA Inspection: MECHANICAL & CERAMIC SOLUTIONS INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MECHANICAL & CERAMIC SOLUTIONS INC. in 730 SUPERIOR STREET CARNEGIE INDUSTRIAL PARK, CARNEGIE, PA 15106 (NAICS 423320). OSHA activity number 339567356.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MECHANICAL & CERAMIC SOLUTIONS INC.
- Site address
- 730 SUPERIOR STREET CARNEGIE INDUSTRIAL PARK
- City
- CARNEGIE
- State
- PA
- ZIP
- 15106
- Mailing
- P.O. BOX 536, CARNEGIE, PA 15106
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423320
- Employees
- 45
- Ownership type
- A
Citations
11 citations on file for this inspection.
5(a)(1)
- Issued
- Feb 27, 2014
- Abate by
- Mar 25, 2014
- Penalty
- Initial $2,800 · Current $2,100 Reduced
General-duty citation text
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to struck-by and crushed-by hazards created by the use of industrial storage racks which were not anchored to the floor: a) Building 16, Brick Saw Bay Area, 730 Superior Street, Carnegie, Pennsylvania, 15106. Observed on or about January 30, 2014, employees were using industrial storage racks that were not anchored to the floor. The industrial storage racks were used to store pallets of ceramic bricks and other materials. The industrial storage racks were at risk of tipping over while being loaded or unloaded by forklifts. Employees loading the industrial storage racks and employees working in the area of the industrial storage racks were exposed to crushed-by and struck-by hazards. b) Building 29, 730 Superior Street, Carnegie, Pennsylvania, 15106. Observed on or about January 30, 2014, employees were using industrial storage racks which were not anchored to the floor. The industrial storage racks were used to store various types of materials and equipment. The industrial storage racks were located along the interior walls of Building 29. Employees loading the industrial storage racks and employees working in the area of the industrial storage racks were exposed to crushed-by and struck-by hazards.
Recent events (2)
- — I (S) $2100
- — Z (S) $2800
1910.23 C01
- Issued
- Feb 27, 2014
- Abate by
- Mar 25, 2014
- Penalty
- Initial $2,800 · Current $1,820 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: Note: Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard: (a) Warehouse Building, 730 Superior Street, Carnegie, Pennsylvania 15106: On or about January 30, 2014, no railing was provided along the open-sided floor approximately 4 feet 2 inches above the lower dock floor area. Employee(s) retrieving materials from or placing materials into the warehouse were exposed to potential fall hazards created by the lack of guardrail around the open pit.
Recent events (2)
- — I (S) $1820
- — Z (S) $2800
1910.178 L01 I
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $2,800 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(i): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l): a) Main Shop Area, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 27, 2014, the employer did not ensure all employees assigned to operate forklifts were certified. Employees working in areas of the facility where forklifts were being used were exposed to struck-by hazards.
Recent events (2)
- — I (S) $2100
- — Z (S) $2800
1910.178 L01 II
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a power industrial truck: a) Main Shop Area, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 27, 2014, the employer did not ensure all employees assigned to operate forklifts were trained to operate a forklift. Employees working in areas where forklifts were being used were exposed to struck-by hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $3,500 · Current $2,275 Reduced
General-duty citation text
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, the electrical panel box used to control the warehouse ceiling lights was not installed in a neat and workmanlike manner. Deficiencies with the panel box included, but were not limited to, missing labels, exposed conductors, a missing cover, and a missing dead front. Employees using a switch located inside the panel box to operate the ceiling lights in the warehouse were exposed to the hazard of electric shock and burns.
Recent events (2)
- — I (S) $2275
- — Z (S) $3500
1910.303 E01 I
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
1910.303(e)(1)(1): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified was not placed on the electrical equipment that was used: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical panel box was not marked with the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified. Employees using a switch inside the panel box to operate the ceiling lights in the warehouse were exposed to the hazard of electric shock and burns.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 E01 II
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(e)(ii): Markings were not provided on electrical equipment giving voltage, current, wattage, and other ratings as necessary: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical panel box was not equipped with markings giving the voltage, current, wattage, and other ratings as necessary. Employees using a switch inside the panel box to operate ceiling lights in the warehouse were exposed to the hazard of electric shock and burns. b) Warehouse, southeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, fuse boxes and safety switches located on a wall between the bay doors were not equipped with labels giving the voltage, current, wattage, and other ratings as necessary. Employees accessing the warehouse through the bay door were exposed to hazard electric shock and burns.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 D
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(d): Panelboards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical panel box was not equipped with a dead front. Employees using switches inside the panel box to operate the warehouse ceiling lights were exposed to the hazard of electric shock and burns.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 V
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(v): Illumination was not provided for all working spaces about service equipment, switchboards, panelboards, and motor control centers installed indoors. Additional lighting fixtures are not required where the working space is illuminated by an adjacent light source. In electric equipment rooms, the illumination may not be controlled by automatic means only: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, employees were required to use switches inside an electric panel box in the absence of illumination. Employees using the electric panel switches to operate the warehouse ceiling lights before sunrise were exposed to the hazard of electric shock and burns.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures: a) Warehouse, northeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical panel box was not effectively closed because the cover was missing. Energized components inside the electric panel were exposed. Employees using switches inside the electric panel box to operate ceiling lights in the warehouse were exposed to the hazard of electric shock and burns. b) Warehouse, southeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical junction box located directly above two Square D brand fuse boxes on an interior wall between the bay doors was not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. Conductors located inside the junction box were exposed due to a missing front cover on the junction box. Employees using the bay door to access the warehouse were exposed to the hazard of electric shock and burns. c) Warehouse, southeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, a Square D brand fuse box (220 Volt) was open. The fuse box could not be closed due to a yellow rope which was tied to components within the fuse box. Employees accessing the warehouse through the bay door were exposed to the hazard of electric shock and burns. d) Main Shop Area, east wall, brick saw bay area, Building 16, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, an electrical junction box located beneath a Square D brand safety switch labeled "Single Phase 240 with neutral A" (yellow making/hand written) was not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures. The front of the junction box was open and the conductors inside were exposed. Employees working in the area of the industrial storage racks were exposed to the hazard of electric shock and fire. e) Warehouse, southeast wall, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, the metal box housing the bay door switch was broken. Employees using the bay door switch were exposed to the hazard of electric shock and burns.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.178 A06
- Issued
- Feb 27, 2014
- Abate by
- Mar 11, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(a)(6): Nameplates or markings for powered industrial trucks were not in place: a) Main Shop Area, 730 Superior Street, Carnegie, Pennsylvania 15106: Observed on or about January 30, 2014, the employer did not ensure all nameplates and markings were in place on an orange LPG Toyota brand forklift (unknown model or serial number). The forklift was used to move materials between the yard, warehouse, and buildings 16 and 29. There were no markings on the forklift to identify the model number, serial number, rated capacity and information. Employees using the forklift to move materials throughout the facility were exposed to struck-by hazards.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Mechanical & Ceramic Solutions INC.
View Mechanical & Ceramic Solutions INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423320)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339567356.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.