Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MARIANO PRESS/DBA MERCURY PRINTING,INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MARIANO PRESS/DBA MERCURY PRINTING,INC. in 14 VERONICA AVE., SOMERSET, NJ 08873 (NAICS 323110). OSHA activity number 339568446.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mariano Press/Dba Mercury Printing,Inc. — free Get an email when a new federal OSHA severe-injury report for Mariano Press/Dba Mercury Printing,Inc. is published. One employer, no account, unsubscribe in one click.
Site address
14 VERONICA AVE.
City
SOMERSET
State
NJ
ZIP
08873
Mailing
14 VERONICA AVE., SOMERSET, NJ 08873
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
323110
Employees
16
Ownership type
A

3 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 16 exposed
Issued
Jul 22, 2014
Abate by
Aug 15, 2014
Penalty
Initial $1,360 · Current $1,100 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:    a) Mariano Press Somerset, NJ site - Forklift battery charging station.    An eye wash facility was not provided where the electric powered industrial vehicle batteris are maintained and charged.    Condititon noted on or about 1/30/2014.
Recent events (2)
  • — I (S) $1100
  • — Z (S) $1360

1910.303 G01 II

Serious Gravity 1 3 instances 16 exposed
Issued
Jul 22, 2014
Abate by
Aug 15, 2014
Penalty
Initial $1,020 · Current $760 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    Mariano Press Somerset, NJ site - Electrical panel boxes rated 480V/3phase and 220V/ single phase that control the lights and main power to various machinery being used in the facility were blocked:     a)  Copier Room - The electrical panel was blocked by a desk and a copier.    b) Loading dock - The electrical panels were blocked by the forklift charging station, various printing equipment and other storage containers.    c) Production area - 55 gallon drums of product were stored below the electrical panels causing a tripping hazard.     Condition noted on or about 1/30/2014.
Recent events (2)
  • — I (S) $760
  • — Z (S) $1020

1910.305 B02 I

Other-than-serious 1 instance 3 exposed
Issued
Jul 22, 2014
Abate by
Aug 15, 2014
Penalty
Initial $1,360 · Current $0 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:    a) Mariano Press Somerset, NJ site - Copier room:    Electrical outlet was not provided with a faceplate.    Condition noted on or about 1/30/2014.
Recent events (2)
  • — I (O) $0
  • — Z (S) $1360

View Mariano Press/Dba Mercury Printing,Inc.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339568446.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.