PALMYRA, NY —
OSHA Inspection: FINZER ROLLER
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of FINZER ROLLER in 2085 DIVISION STREET, PALMYRA, NY 14522 (NAICS 326299). OSHA activity number 339571176.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FINZER ROLLER
- Site address
- 2085 DIVISION STREET
- City
- PALMYRA
- State
- NY
- ZIP
- 14522
- Mailing
- 2085 DIVISION STREET, PALMYRA, NY 14522
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326299
- Employees
- 23
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.22 A01
- Issued
- Mar 7, 2014
- Penalty
- Initial $1,951 · Current $1,366 Reduced
General-duty citation text
29 CFR 1910.22(a)(1): Place(s) of employment were not kept clean: a) Crate Building Arewa; on or about 2/4/14: Explosive Wood Dust (Class II) was observed in throughout this area on the tables; outlets and on the floor.
Recent events (2)
- — I (S) $1365.7
- — Z (S) $1951
1910.303 B02
- Issued
- Mar 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: b) Crate Building Area, on or about 2/4/14: A 5.0 HP Shop Vac was used to vacuum Class II wood dust.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 G02
- Issued
- Mar 7, 2014
- Abate by
- Apr 1, 2014
- Penalty
- Initial $2,295 · Current $1,607 Reduced
General-duty citation text
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter: a) Throughout the facility, on or about 2/4/14: Training was not provided annually to employees on the use of fire extinguishers and the hazards involved with incipient stage fire fighting. Last training conducted was July 2011. * ABATEMENT NOTE: By this date the employer must either correct the alleged violation or implement a Fire Safety Policy; as outlined in 29 CFR 1910.38(a) and .39 which includes the evacuation requirements of 29 CFR 1910.157(b).
Recent events (2)
- — I (S) $1606.5
- — Z (S) $2295
More inspections at Finzer Roller
View Finzer Roller's full OSHA safety record →
More inspections in this industry (NAICS 326299)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339571176.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.