Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COSTCO, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of COSTCO, INC. in 3800 N. DIVISION STREET, MORRIS, IL 60450 (NAICS 493120). OSHA activity number 339574469.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Costco, INC. — free Get an email when a new federal OSHA severe-injury report for Costco, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
COSTCO, INC.
Site address
3800 N. DIVISION STREET
City
MORRIS
State
IL
ZIP
60450
Mailing
3800 N. DIVISION STREET, MORRIS, IL 60450
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
142
Ownership type
A

2 citations on file for this inspection.

1910.119 D03 II

Other-than-serious 1 instance 5 exposed
Issued
Jul 28, 2014
Penalty
Initial $4,675 · Current $0 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.     On or about January 30, 2014, Costco, Inc., did not document that the ventilation equipment, for the machinery room, complied with recognized and generally accepted good engineering practices such as, but not limited to,  IAPMO/ANSI UMC 1-2003 Uniform Mechanical Code.  Specifically, the ventilation was not run on a continuous basis during winter months.     This item was corrected during the inspection.
Recent events (3)
  • — F (O) $0
  • — C (S) $4675
  • — Z (S) $4675

1910.119 J04 I

Other-than-serious 2 instances 5 exposed
Issued
Jul 28, 2014
Abate by
Oct 29, 2014
Penalty
Initial $4,675 · Current $4,000 Reduced
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment     On or about January 30, 2014, Costco, Inc., did not perform the following inspection and tests on process equipment:     a.  An independent inspection was not conducted at least once every five years in accordance with recommended and generally accepted good engineering practices such as, but not limited to, IIAR Bulletin No. 110, Guidelines for: Start-up, Inspection and Maintenance of Ammonia Mechanical Refrigerating Systems, on the following pressure vessels: the High Pressure Receiver, the High Temperature Accumulator, the Medium Temperature Accumulator, and the Low Temperature Accumulator.     b.  Vibration Analysis was not conducted on Compressors # 1 - 9, as recommended by the manufacturer of the equipment, Johnson Controls, Inc.  The installation, operation, and maintenance manual specifies that vibration analysis should be conducted upon installation and every 6 months thereafter.     Abatement certification and documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).