OSHA Inspection: PAUL MATTUCHIO, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PAUL MATTUCHIO, INC. in 366 2ND STREET, EVERETT, MA 02149 (NAICS 423930). OSHA activity number 339576274.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Paul Mattuchio, INC. — free Get an email when a new federal OSHA severe-injury report for Paul Mattuchio, INC. is published. One employer, no account, unsubscribe in one click.
Site address
366 2ND STREET
City
EVERETT
State
MA
ZIP
02149
Mailing
366 2ND STREET, EVERETT, MA 02149
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
35
Ownership type
A

12 citations on file for this inspection.

1910.178 F02

Serious Gravity 1 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $2,100 · Current $1,090 Reduced
29 CFR 1910.178(f)(2): The storage and handling of liquefied petroleum gas fuel was not in accordance with NFPA Storage and Handling of Liquefied Petroleum Gases (NFPA No. 58-1969), which is incorporated by reference as specified in 29 CFR 1910.6:    (a) Location - 366 2nd Street, Everett, MA:    On or about 2/4/2014, liquid petroleum gas fuel cylinders for forklifts were not stored in approved enclosures to prevent damage.
Recent events (2)
  • — I (S) $1090
  • — Z (S) $2100

1910.212 A03 II

Serious Gravity 5 4 instances 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $3,500 · Current $1,820 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    (a) Location - 366 2nd Street, Everett, MA:    On or about 2/4/2014, alligator shears were not guarded.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $3500

1910.303 B02

Serious Gravity 5 3 instances 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $4,200 · Current $2,270 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    (a) Location - 366 2nd Street, Everett, MA:    On or about 2/4/2014, relocatable power taps were used in an industrial setting and in conjunction with extension cords.
Recent events (2)
  • — I (S) $2270
  • — Z (S) $4200

1910.305 A02 X

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points.  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, an extension cord used to power a reciprocating saw was ran through a hole in the wall over a piece of metal projecting from the wall and across an aisle where materials are transported.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, an extension cord was ran through a hole in the wall.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, an extension cord was worn in a way that strain relief was not provided.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, an extension cord that was damaged was not removed from service.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 3 instances 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $3,500 · Current $1,820 Reduced
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    (a) Location - 366 2nd Street, Everett, MA:    On or about 2/4/2014, electrical service control panels within the building were not covered.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $3500

1910.305 B01 II

Serious Gravity 5 3 instances 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, breaker openings in electrical service control panels were not covered.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 C04

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(c)(4): Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, light switches within the facility were uncovered.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 A05

Other-than-serious 1 instance 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.23(a)(5): 29 CFR 1910.23(a)(5): For every pit and/or trap door floor opening, while the cover was not in place, was not constantly attended by someone or was not protected on all exposing sides by removable standard railings:    (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, a floor opening around the building's sprinkler system was uncovered, and other means to prevent employees from falling into the floor opening were not provided.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E03

Other-than-serious 2 instances 10 exposed
Issued
Mar 10, 2014
Abate by
Apr 12, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  (a) Location - 366 2nd Street, Everett, MA:  On or about 2/4/2014, mounted portable fire extinguishers available within the facility were not within service date for their annual maintenance checks.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Paul Mattuchio, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339576274.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.