Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: JACK SPRING ELECTRICAL CONTRACTORS, INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of JACK SPRING ELECTRICAL CONTRACTORS, INC. in 135 CYPRESS PARK DR., BENTON, LA 71006 (NAICS 238210). OSHA activity number 339576530.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jack Spring Electrical Contractors, INC. — free Get an email when a new federal OSHA severe-injury report for Jack Spring Electrical Contractors, INC. is published. One employer, no account, unsubscribe in one click.
Site address
135 CYPRESS PARK DR.
City
BENTON
State
LA
ZIP
71006
Mailing
6307 LINWOOD AVE., SHREVEPORT, LA 71106
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

3 citations on file for this inspection.

1910.269 A03

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 1, 2014
Abate by
Aug 13, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.269(a)(3): The employer did not determine existing conditions related to the safety of the work to be performed before work on or near electric lines or equipment was started:   On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer failed to identify all phases of energy supplying electricity to electrical parts upon which employees were working for the purpose of repairing a pad mounted transformer.
Recent events (2)
  • — I (S) $7000
  • — Z (S) $7000

1910.269 M03 II

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 1, 2014
Abate by
Aug 16, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.269(m)(3)(ii): All switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized were not opened and rendered inoperable, when its design permitted.      On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer did not clearly and properly identify, isolate then deenergize all electric energy before making repairs to the electrical system at the outdoor recreation area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.269 L02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Aug 1, 2014
Abate by
Aug 13, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.269(l)(2): The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than set forth in Tables R-6 through R-10:   On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer did not ensure that employees removing parts from an energized transformer did not approach the exposed parts with uninsulated tools.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

View Jack Spring Electrical Contractors, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339576530.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.