BENTON, LA —
OSHA Inspection: JACK SPRING ELECTRICAL CONTRACTORS, INC.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of JACK SPRING ELECTRICAL CONTRACTORS, INC. in 135 CYPRESS PARK DR., BENTON, LA 71006 (NAICS 238210). OSHA activity number 339576530.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- JACK SPRING ELECTRICAL CONTRACTORS, INC.
- Site address
- 135 CYPRESS PARK DR.
- City
- BENTON
- State
- LA
- ZIP
- 71006
- Mailing
- 6307 LINWOOD AVE., SHREVEPORT, LA 71106
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 30
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.269 A03
- Issued
- Aug 1, 2014
- Abate by
- Aug 13, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.269(a)(3): The employer did not determine existing conditions related to the safety of the work to be performed before work on or near electric lines or equipment was started: On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer failed to identify all phases of energy supplying electricity to electrical parts upon which employees were working for the purpose of repairing a pad mounted transformer.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.269 M03 II
- Issued
- Aug 1, 2014
- Abate by
- Aug 16, 2014
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(m)(3)(ii): All switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be deenergized were not opened and rendered inoperable, when its design permitted. On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer did not clearly and properly identify, isolate then deenergize all electric energy before making repairs to the electrical system at the outdoor recreation area.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
1910.269 L02
- Issued
- Aug 1, 2014
- Abate by
- Aug 13, 2014
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(2): The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than set forth in Tables R-6 through R-10: On or about 02/06/2014, at the Cypress Black Bayou Recreation Area, the employer did not ensure that employees removing parts from an energized transformer did not approach the exposed parts with uninsulated tools.
Recent events (2)
- — I (S) $0
- — Z (S) $7000
More inspections at Jack Spring Electrical Contractors, INC.
View Jack Spring Electrical Contractors, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in LA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339576530.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.