LAKE ELSINORE, CA —
OSHA Inspection: USDA FOREST SERVICE - CLEVELAND NF
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of USDA FOREST SERVICE - CLEVELAND NF in EL CHARISO FIRE STATION 32353 ORTEGA HIGHWAY, LAKE ELSINORE, CA 92530 (NAICS 115310). OSHA activity number 339581324.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- USDA FOREST SERVICE - CLEVELAND NF
- Site address
- EL CHARISO FIRE STATION 32353 ORTEGA HIGHWAY
- City
- LAKE ELSINORE
- State
- CA
- ZIP
- 92530
- Mailing
- 10845 RANCHO BERNARDO ROAD, SUITE 200, SAN DIEGO, CA 92127
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 115310
- Employees
- 10
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.37 B07
- Issued
- Mar 19, 2014
- Abate by
- Apr 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(7): Each exit sign must have the word "Exit" in plainly legible letters not less than six inches (15.2 cm) high, with the principal strokes of the letters in the word "Exit" not less than three-fourths of an inch (1.9 cm) wide. Engine bay exits: On or about 29JAN14, exit signs posted had lettering measuring less than the required six inches high.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Mar 19, 2014
- Abate by
- Apr 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: (a) Kitchen: On or about 29JAN14, a fire extinguisher was not inspected monthly. (b) Engine bay: On or about 29JAN14, a fire extinguisher was not inspected monthly. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 157(e)(2), which was contained in OSHA inspection number 910625, citation number 1, item number 2, and was affirmed as a final order on July 29, 2013, with respect to a workplace located at 602 S. Tippecanoe Av., San Bernardino, CA 92408.
Recent events (1)
- — Z (R) $0
1910.253 B04 I
- Issued
- Mar 19, 2014
- Abate by
- Apr 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire: Gas House, On or about 29JAN14, a compressed gas cylinder containing oxygen was stored with road flares and muriatic acid. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 253(b)(4)(i), which was contained in OSHA inspection number 911912, citation number 1, item number 7, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 28500 Highway 243, Mountain Center, CA 92561.
Recent events (1)
- — Z (R) $0
1910.303 B07 I
- Issued
- Mar 19, 2014
- Abate by
- Apr 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: (a) Engine bay East exit: On or about 29JAN14, 120VAC live conductors were exposed to inadvertent employee contact where openings in a switch box was left uncovered, and the cover was not effectively secured. (b) Engine bay water fountain: On or about 29JAN14, 220VAC live conductors were exposed to inadvertent employee contact where an opening in a switch box was left uncovered. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 303(b)(7)(i), which was contained in OSHA inspection number 911911, citation number 1, item number 11, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV A
- Issued
- Mar 19, 2014
- Abate by
- Apr 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: Training room: On or about 29JAN14, flexible cords were used for over 90 days one year to provide 120VAC service to a television and VCR. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 911911, citation number 1, item number 15, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333.
Recent events (1)
- — Z (R) $0
More inspections at Usda Forest Service - Cleveland NF
View Usda Forest Service - Cleveland NF's full OSHA safety record →
More inspections in this industry (NAICS 115310)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339581324.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.