MIAMI, FL —
OSHA Inspection: GANCEDO LUMBER CO., INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of GANCEDO LUMBER CO., INC. in 9300 NW 36TH AVENUE, MIAMI, FL 33147 (NAICS 444190). OSHA activity number 339581886.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GANCEDO LUMBER CO., INC.
- Site address
- 9300 NW 36TH AVENUE
- City
- MIAMI
- State
- FL
- ZIP
- 33147
- Mailing
- 9300 NW 36TH AVENUE, MIAMI, FL 33147
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 444190
- Employees
- 76
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.26 C03 VII
- Issued
- Apr 3, 2014
- Penalty
- Initial $2,975 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.26(c)(3)(vii): Ladders were used as a brace, skid, guy, or gin pole, gangway, or for other uses than that for which they were intended, unless specifically recommended for use by the manufacturer: a. On or about February 11, 2014, at the east side shear/cutting area of the above addressed jobsite, an employee was exposed to a fall hazard while using a closed A-type ladder to access the platform of trailer.
Recent events (2)
- — I (S) $1785
- — Z (S) $2975
1910.23 E02
- Issued
- Apr 3, 2014
- Abate by
- Apr 9, 2014
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge of tread: a. On or about February 11, 2014, at the engineering department of the above addressed jobsite, an employee was exposed to a fall hazard while using a stair that lacked a midrail on its railing system.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.184 E01
- Issued
- Apr 3, 2014
- Abate by
- Apr 9, 2014
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach: a. On or about February 11, 2014, at the west side of the above addressed jobsite, a chain sling had its identification tag not legible, which can expose employees to a struck by hazard in the event of overloading.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.304 G05
- Issued
- Apr 3, 2014
- Abate by
- Apr 9, 2014
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a. On or about February 11, 2014, at the east side storage area of the above addressed jobsite, a refrigerator (i.e. Sanyo) lacked a ground prong on its attachment plug, exposing employees to an electrical hazard. b. On or about February 11, 2014, at the east side storage area of the above addressed jobsite, a fan was energized from an electrical receptacle which lacked a connection to ground, exposing employees to an electrical hazard.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.305 B01 I
- Issued
- Apr 3, 2014
- Abate by
- Apr 9, 2014
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a. On or about February 11, 2014, at the east side shear area of the above addressed jobsite, employees were exposed to an electrical hazard while working in close proximity to conductors entering an electrical cabinet which were not totally enclosed within conduit.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.305 B02 I
- Issued
- Apr 3, 2014
- Abate by
- Apr 17, 2014
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a. On or about February 11, 2014, at the west side of the above addressed jobsite, employees were exposed to an electrical hazard while working in close proximity to an electrical junction box which lacked a coverplate.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1910.305 E01
- Issued
- Apr 3, 2014
- Abate by
- Apr 17, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: a. On or about February 11, 2014, at the west side of the above addressed jobsite, employees were exposed to an electrical hazard while working in close proximity to an electrical junction box which was not installed so as to prevent water from getting accumulated within the box.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Gancedo Lumber CO., INC.
View Gancedo Lumber CO., INC.'s full OSHA safety record →
More inspections in this industry (NAICS 444190)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339581886.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.