WILKES BARRE, PA —
OSHA Inspection: LIFE SAFETY GROUP LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of LIFE SAFETY GROUP LLC in MOHEGAN SUN CASINO 1280 HIGHWAY 315, WILKES BARRE, PA 18702 (NAICS 238210). OSHA activity number 339588303.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LIFE SAFETY GROUP LLC
- Site address
- MOHEGAN SUN CASINO 1280 HIGHWAY 315
- City
- WILKES BARRE
- State
- PA
- ZIP
- 18702
- Mailing
- 223 SALT LICK ROAD, SAINT PETERS, MO 63376
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 12
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.416 A01
- Issued
- Jul 3, 2014
- Abate by
- Jul 10, 2014
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: a) Mohegan Sun Casino and Hotel at Pocono Downs, Wilkes-Barre, PA: An employee was performing work in an electrical panel box, located in the hotel lobby electrical room, without de-energizing the circuit. The employee sustained an arc flash injury when an non-insulated tool contacted the energized buss bar inside the panel box, on or about February 14, 2014. Abatement Certification Required.
Recent events (1)
- — Z (S) $2800
1926.95 A
- Issued
- Jul 3, 2014
- Abate by
- Aug 20, 2014
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided: a) Mohegan Sun Casino and Hotel at Pocono Downs, Wilkes-Barre, PA: An employee working in an energized 277/480 volt panel box was not wearing the proper personal protective equipment needed for electrical and arc flash hazards, on or about February 14, 2014. Abatement Certification Required.
Recent events (1)
- — Z (S) $2800
1926.301 A
- Issued
- Jul 3, 2014
- Abate by
- Aug 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.301(a): Unsafe hand tool(s) were issued or permitted to be used: a) Mohegan Sun Casino and Hotel at Pocono Downs, Wilkes-Barre, PA: A non-insulated screwdriver was used by an employee while working in an energized 277/480 volt 3 phase panel box, on or about February 14, 2014. Abatement Certification Required.
Recent events (1)
- — Z (S) $0
More inspections in this industry (NAICS 238210)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339588303.