Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NOAA NATIONAL WEATHER SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOAA NATIONAL WEATHER SERVICE in 7600 SAND POINT WAY NE, BUILDING 1, SEATTLE, WA 98115 (NAICS 541990). OSHA activity number 339588691.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Noaa National Weather Service — free Get an email when a new federal OSHA severe-injury report for Noaa National Weather Service is published. One employer, no account, unsubscribe in one click.
Site address
7600 SAND POINT WAY NE, BUILDING 1
City
SEATTLE
State
WA
ZIP
98115
Mailing
7600 SAND POINT WAY NE, SEATTLE, WA 98115
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
29
Ownership type
D

4 citations on file for this inspection.

1910.303 B02

Repeat Gravity 1 3 instances 29 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:    a) Facility, where equipment not used as listed or labeled included:     1. Cubicle, where an APC (uninterrupted power source) relocatable power tap was daisy chained with the Perma Power relocatable power tap and used to supply power to computer equipment.   2. Cubicle, where an APC (uninterrupted power source) relocatable power tap was daisy chained with a relocatable power tap and used to supply power to computer equipment.   3. Electronic Tech Shop, where two relocatable power taps were permanently attached to the metal shelving and used to supply power to electronic equipment.    The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829.015 citation no. 2, item no. 4, issued on June 4, 2013 with respect to a workplace at Pasco, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 107939 citation no. 2, item no. 1, issued on November 15, 2011 with respect to a workplace at Mukilteo, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097335, citation no. 2, item no. 1, issued on April 28, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097343, citation no. 1, item no. 1, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097319, citation no. 2, item no. 2, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097384, citation no. 1, item no. 1, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096287, citation no. 2, item no. 1, issued on October 2, 2009 with respect to a workplace at Port Orchard, WA.
Recent events (1)
  • — Z (R) $0

1910.305 G01 IV A

Repeat Gravity 1 1 instance 29 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:   a) Avalanche Center Cubicle, where an extension cord was used to supply power to computer equipment and a portable fan.   The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829.015 citation no. 2, item no. 4, issued on June 4, 2013 with respect to a workplace at Pasco, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 107939 citation no. 1, item no. 1, issued on November 15, 2011 with respect to a workplace at Mukilteo, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097285 citation no. 1, item no. 7, issued on April 27, 2010 with respect to a workplace at Seattle, WA.
Recent events (1)
  • — Z (R) $0

1910.36 G02

Other-than-serious 1 instance 29 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a) UPS Room, where the placement of the placement of computer cart reduced the aisleway width to 21 inches.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 29 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:  a) UPS Room , where items including a board, a small table, and filters, were stored in front of the circuit panels PPA and PPB.
Recent events (1)
  • — Z (O) $0

View Noaa National Weather Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339588691.