WARRENVILLE, IL —
OSHA Inspection: TWO BROTHERS BREWING COMPANY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of TWO BROTHERS BREWING COMPANY in 30W315 CALUMET AVE., WARRENVILLE, IL 60555 (NAICS 312120). OSHA activity number 339590788.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TWO BROTHERS BREWING COMPANY
- Site address
- 30W315 CALUMET AVE.
- City
- WARRENVILLE
- State
- IL
- ZIP
- 60555
- Mailing
- 30W315 CALUMET AVE., WARRENVILLE, IL 60555
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 312120
- Employees
- 34
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.37 A03
- Issued
- Mar 26, 2014
- Abate by
- Jun 1, 2014
- Penalty
- Initial $3,500 · Current $1,750 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: (a) Southeast, packaging hall: on February 19, 2014, the southeast corner emergency exit door access and associated egress path were blocked a pallet containing empty bottles and a bottling line in-feed tray. (b) Southwest, packaging hall: on February 19, 2014, the southwest corner emergency exit door access and associated egress path were blocked by a bottling line conveyor. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).
Recent events (2)
- — I (S) $1750
- — Z (S) $3500
1910.303 B02
- Issued
- Mar 26, 2014
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Southwest, packaging hall employees' desk and Citronix coding workstation, orange unmarked extension cord and orange extension cord Cat#112-5 E70726: on February 19, 2014, employees were exposed to electric shock hazard where listed and labeled electrical equipment was not installed and used in accordance with the manufacturers' provisions and other applicable listing standards for that type of equipment. Energized extension cords were not rated for use in wet locations and remained in service where damaged outer jacket was wrapped with black electrical tape. (b) Southwest, packaging hall employees' desk, Ace Hardware relocatable power tap model no. 33543 E116852 4: on February 19, 2014, employees were exposed to possible equipment overheating resulting in fire and burn hazards where listed and labeled electrical equipment was not installed and used in accordance with the manufacturer's provisions and other applicable listing standards for that type of equipment. Energized relocatable power tap was not used and installed as designed because it was utilized in the industrial setting wet location as a substitute for fixed wiring and not directly connected to permanently installed branch circuit receptacle. (c) Southwest, packaging hall by Sigrist sensors, Belkin travel surge protector model no. BE 107201 08: on February 19, 2014, employees were exposed to fire and burn hazards from possible equipment overheating and other malfunctions where listed and labeled electrical equipment was not installed and used in accordance with the manufacturer's provisions and other applicable listing standards for that type of equipment. Energized relocatable power tap was not used and installed as designed because it was utilized in the industrial setting wet location without direct connection to permanently installed branch circuit receptacle, and connected in series to other relocatable power tap via extension cord. There is no abatement certification or documentation required for this item.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.303 G02 I
- Issued
- Mar 26, 2014
- Abate by
- Jun 1, 2014
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Southwest, packaging hall, citronix Ci700 coding workstation Banner date stamp monitor vertical guide post and horizontal adjustment bar: on February 19, 2014, employees were exposed to electric shock hazard where required to adjust date stamping equipment by contacting energized components. Abatement certification is required of this item in accordance with the requirements of 1903.19(c).
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 G01 IV A
- Issued
- Mar 26, 2014
- Abate by
- Jun 1, 2014
- Penalty
- Initial $4,200 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Northwest, fermentation tanks, multiple unmarked extension cords and flexible cords: on February 19, 2014, employees were exposed to electric shock hazard when walking in-between fermentation tanks to check temperature monitors, perform any cleaning tasks, and other assignments. Energized flexible cables and extension cords were suspended horizontally between tanks to connect to each temperature monitor placed on tanks above the adjacent floor. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $2100
- — Z (S) $4200
1910.305 G02 II
- Issued
- Mar 26, 2014
- Abate by
- Jun 1, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap: Northwest, fermentation tanks, multiple unmarked extension cords and flexible cords: on February 19, 2014, employees were exposed to electric shock hazard when walking in-between fermentation tanks to check temperature monitors, perform any cleaning tasks, and any other assignments. Energized flexible cables and extension cords were spliced in multiple locations. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07
- Issued
- Mar 26, 2014
- Abate by
- Jun 1, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7): Electrical equipment was not installed in a neat and workmanlike manner: Northwest, fermentation tanks, multiple unmarked extension cords and flexible cables: on February 19, 2014, electrical installation powering temperature monitors on fermentation tanks was not completed in a neat and workmanlike manner due to extension cords and flexible cables spliced and wrapped with black electrical tape, and suspended horizontally overhead between tanks as a substitute for fixed wiring. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at TWO Brothers Brewing Company
View TWO Brothers Brewing Company's full OSHA safety record →
More inspections in this industry (NAICS 312120)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339590788.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.