OSHA Inspection: ACTIVE WIRING COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ACTIVE WIRING COMPANY in 1906 FAIRVIEW, CALDWELL, ID 83605 (NAICS 238210). OSHA activity number 339592859.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Active Wiring Company — free Get an email when a new federal OSHA severe-injury report for Active Wiring Company is published. One employer, no account, unsubscribe in one click.
Site address
1906 FAIRVIEW
City
CALDWELL
State
ID
ZIP
83605
Mailing
P.O. BOX 426, COTTONWOOD, ID 83522
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 28, 2014
Abate by
Mar 26, 2014
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.    a) Circuit Breaker Panel on the First Floor of Medical Office Building: On or about February 14, 2014, employees worked bare-handed on an energized panel rated at 800 Amps and 480 Volts while adding fingers to install circuit breakers.  The employer had not trained employees in the recognition and avoidance of hazards while working on energized panels or to de-energize such panels prior to the commencement of work.    Abatement certification and documentation are required for this item.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1926.416 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 28, 2014
Abate by
Mar 26, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.416(a)(1): The employer permitted employees to work in such proximity to any part of an electric power circuit so that the employee could contact an electric power circuit in the course of work, and employees were not protected against electric shock by de-energizing the circuit and grounding it or by guarding it effectively by insulation or other means.   a) Circuit Breaker Panel on the First Floor of Medical Office Building: On or about February 14, 2014, employees worked bare-handed on an energized panel rated at 800 Amps and 480 Volts while adding fingers to install circuit breakers.  Employees performed work on an energized panel as opposed to de-energizing the circuit and grounding it, or by guarding the energized circuit by insulation.   Abatement certification and documentation are required for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.95 A

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 28, 2014
Abate by
Mar 26, 2014
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, and maintained in a sanitary and reliable condition when it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact.    a) Circuit Breaker Panel on the First Floor of Medical Office Building: On or about February 14, 2014, employees worked bare-handed without any personal protective equipment on an energized panel rated at 800 Amps and 480 Volts while adding fingers to install circuit breakers.      NOTE: National Fire Proteciton Association NFPA 70E-2009, Table 130.7(C)(9) defines work on panelboards or switchboards rated >240 Volts and up to 600 Volts as hazard/risk category 2.  Personal protective equipment required by this category includes, but is not limited to, flame resistant (FR) clothing with a minimum arc rating of 8, a hard hat, safety glasses or safety goggles, hearing protection, leather gloves and leather work shoes.    Abatement certification and documentation are required for this item.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800