Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: BRIDGESTONE GCS, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BRIDGESTONE GCS, LLC in 8989 HWY 17, TOCCOA, GA 30577 (NAICS 238210). OSHA activity number 339594277.

Watch Bridgestone GCS, LLC — free Get an email when a new federal OSHA severe-injury report for Bridgestone GCS, LLC is published. One employer, no account, unsubscribe in one click.
Site address
8989 HWY 17
City
TOCCOA
State
GA
ZIP
30577
Mailing
616-B MEDLOCK ROAD, DECATUR, GA 30033
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
4
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $1600.00
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  On or about February 18, 2014:  a) Employees were exposed to electrical shock and or burns when the employer installed nonmetallic sheathing cable for temporary power to use within the structure being constructed. The cable being used was laid upon the ground and was not protected.
Recent events (1)
  • — Z (S) $1600

1926.405 A02 II A

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $1600.00
29 CFR 1926.405(a)(2)(ii)(A): Temporary wiring feeder conductors were not run as multiconductor cord or cable assemblies or within raceways; or, where not subject to physical damage, run as open conductors on insulators not more than 10 feet apart:  On or about February 18, 2014:  a) Employees were exposed to electrical shock and burns when the employer failed to protect nonmetallic sheathed cable that was being used for temporary power on the work site.
Recent events (1)
  • — Z (S) $1600

1926.416 A01

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $2400.00 · Current $2400.00
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  On or about February 18, 2014:  a) Employers were exposed to electrical shock or burns when the employer failed properly guard the non-metallic sheathed cable that had been spliced and was covered by electrical tape as a form of insulation.
Recent events (1)
  • — Z (S) $2400

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339594277.