BELLMAWR, NJ ·
OSHA Inspection: EVERGREEN PRINTING COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of EVERGREEN PRINTING COMPANY in 101 HAAG AVE, BELLMAWR, NJ 08031 (NAICS 323111). OSHA activity number 339598112.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EVERGREEN PRINTING COMPANY
- Site address
- 101 HAAG AVE
- City
- BELLMAWR
- State
- NJ
- ZIP
- 08031
- Mailing
- 101 HAAG AVE, BELLMAWR, NJ 08031
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323111
- Employees
- 135
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.101 B
- Issued
- Apr 29, 2014
- Abate by
- May 23, 2014
- Penalty
- Initial $3,600 · Current $2,700 Reduced
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: a)Monitoring Room: Flammable compressed gasses in cylinders were stored near unprotected electrical connections on or about 2/6/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $2700
- · Z (S) $3600
1910.303 B01 I
- Issued
- Apr 29, 2014
- Abate by
- May 23, 2014
- Penalty
- Initial $6,300 · Current $4,725 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(i): Electrical equipment was not free from recognized hazards likely to cause death or serious physical harm, in that the employer did not ensure that the electrical equipment had listing or labeling identifying the purpose and suitability for installation and use in conformity with the provisions of this subpart: a)"A" Press area: Employees were exposed to a hand made 440 Volt electrical enclosure on or about 2/6/14. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $4725
- · Z (S) $6300
1910.303 B07 IV
- Issued
- Apr 29, 2014
- Abate by
- May 23, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating: a)"A" Press Area: Employees were exposed to a handmade metal enclosure for 440 Volt service which had a bent corner exposing live parts on or about 2/6/14. b)Area behind Komori Press: Employees were exposed to a broken 3 prong electrical recepticle in a junction box on or about 2/6/14. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 G01
- Issued
- Apr 29, 2014
- Abate by
- Jun 16, 2014
- Penalty
- Initial $2,700 · Current $2,025 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment: a)Server Room/Pre-Press: Clearance to the main 120 Volt electrical panel box was limited to 14 inches where employees work in the server room on or about 2/6/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $2025
- · Z (S) $2700
1910.303 G02 I
- Issued
- Apr 29, 2014
- Abate by
- Jun 16, 2014
- Penalty
- Initial $4,500 · Current $3,375 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a)Monitoring Room: Employees were exposed to unsecured or unprotected live electric parts in an open sided cabinet on or about 2/6/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $3375
- · Z (S) $4500
1910.305 A02 I
- Issued
- Apr 29, 2014
- Abate by
- Jun 16, 2014
- Penalty
- Initial $4,500 · Current $3,375 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installations rated 600 volts, nominal, or less were used for purposes other than those permitted in subparagraphs (A), (B) and (C) of this paragraph: a)Monitoring Room: Employees were exposed to temporary wiring used to power intruments in a permanent manner on or about 2/6/14. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
- · I (S) $3375
- · Z (S) $4500
More inspections in this industry (NAICS 323111)